Hardware manual
Installation and parameter setup for communication profiles
45
Fieldbus parameters
The Application-specific setting column is a setup for speed/torque control, using
ABB drives profile and PPO type 5.
Parameter
Application-specific
setting
Function/Information
COMMUNICATION INITIALISATION AND SUPERVISION
50.01 FBA ENABLE (1) ENABLE Initialises communication between drive and fieldbus
adapter module.
50.02 COMM LOSS FUNC (1) FAULT Selects how the drive reacts in a fieldbus
communication break.
50.03 COMM LOSS T OUT 0.3 Defines the time between communication break
detection and the action selected with parameter 50.02
COMM LOSS FUNC.
50.04 FBA REF1 MODESEL (2) SPEED Selects the fieldbus reference FBA REF1 scaling and
the actual value, which is sent to the fieldbus (FBA
ACT1). ABB Drives Profile integer value 20000
corresponds to parameter 19.01 SPEED SCALING
value. Signal 01.01 Motor speed rpm is sent to the
fieldbus as an actual value.
50.05 FBA REF2 MODESEL (1) TORQUE Selects the fieldbus reference FBA REF2 scaling and
the actual value, which is sent to the fieldbus (FBA
ACT2). ABB Drives Profile integer value 10000
corresponds to 100% torque value. Signal 01.06 Motor
torque is sent to the fieldbus as an actual value.
FPBA-01 ADAPTER MODULE CONFIGURATION
51.01 FBA TYPE Profibus DP Displays the type of the fieldbus adapter module.
51.02 NODE NUMBER 2 Each device on the Profibus network must have a
unique node number. This parameter is used to define
a node number for the drive it is connected to.
51.03 BAUD RATE 12000 This paremeter indicates the detected communication
speed in kbit/s;12000 = 12 Mbit/s
51.04 TELEGRAM TYPE 5 This parameter indicates the selected telegram type for
the Profibus communication. 5 = PPO Type 5.
51.05 PROFILE 1 This parameter is used to select which communication
profile is used. 1 = ABB Drives profile.