Hardware manual

Installation and parameter setup for communication profiles
39
Fieldbus parameters
The Application-specific setting column is a setup for speed control, using
PROFIdrive profile and PPO type 4.
Parameter
Application-specific
setting
Function/Information
COMMUNICATION INITIALISATION AND SUPERVISION
50.01 FBA ENABLE (1) ENABLE Initialises communication between drive and fieldbus
adapter module.
50.02 COMM LOSS FUNC (1) FAULT Selects how the drive reacts in a fieldbus
communication break.
50.03 COMM LOSS T OUT 0.3 Defines the time between communication break
detection and the action selected with parameter 50.02
COMM LOSS FUNC.
50.04 FBA REF1 MODESEL (2) SPEED Selects the fieldbus reference FBA REF1 scaling and
the actual value, which is sent to the fieldbus (FBA
ACT1).
FPBA-01 ADAPTER MODULE CONFIGURATION
51.01 FBA TYPE Profibus DP Displays the type of the fieldbus adapter module.
51.02 NODE NUMBER 2 Each device on the Profibus network must have a
unique node number. This parameter is used to define
a node number for the drive it is connected to.
51.03 BAUD RATE 12000 Indicates the detected communication speed in kbit/
s;12000 = 12 Mbit/s
51.04 TELEGRAM TYPE 4 Indicates the selected telegram type for the Profibus
communication. 4 = PPO Type 4.
51.05 PROFILE 0 Selects which communication profile is used. 0 =
PROFIdrive.
51.06 T16 SCALE 0 Reference multiplier/actual value divisor for the FPBA-
01. The parameter is only effective when Transparent
16 profile is selected and the drive is using FBA
communication profile.
51.27 FBA PAR REFRESH 1 Validates any changed adapter module configuration
parameter settings.
Note: In the User’s Manual of the fieldbus adapter module, the parameter group number is 1 or A for parameters
51.01…51.26.