User`s manual

Quick start-up guide
20
Configuration connection method 1
To connect to SREA-01, use a cross-over Ethernet cable. Configure your PC to the
same subnet (e.g. IP address 10.200.1.2 and subnet mask 255.255.255.0, other
settings blank).
Use Internet Explorer or Mozilla Firefox and go to location http://10.200.1.1
.
Configuration connection method 2
Install the ABB IP Configuration Tool from the attached CD. When you start the
program, it will search for connected SREA-01 modules. You can change the
network settings of the module by double clicking it.
Use Internet Explorer or Mozilla Firefox and go to location
http://<ip of the SREA-01 module>, e.g. http://10.200.1.1
.
Note: Make sure that your web browser is not using a proxy server for local
connections.
Basic settings of the drive(s)
You should check the communication settings of the drive. Station id/number has
to be unique for each drive! The baud rate selection and parity have to be same on
all drives and SREA-01. You can use for example 9600 bit/s, no parity, 1 stop bit.
ACS350:
Group 52 (Panel Comm) if you are using the panel port for connecting.
Group 53 (EFB Protocol) if you are using FMBA-01 or FRSA-00.
ACS/ACH550:
Group 51 (Ext Comm Module) if you are using RETA-01.
Group 52 (Panel communication) if you are using the panel port for connecting.
Group 53 (EFB Protocol) if you are using the Embedded Modbus connector.
ACS800:
Group 51 (Comm Module Data) if you are using RETA-01.
Group 52 (Standard Modbus) if you are using RMBA-01.
Most important settings of SREA-01
You can change the Ethernet settings under Setup – Ethernet. The login password
can be changed under Setup – Users.
Select the correct drive connection settings under Setup – Modbus.
•Select Physical Interface. If you are using the supplied RJ45-ended cable,
select EIA-232. If you are using the OPCA-02 cable, select EIA-232 (D-sub). If
you are using RS-485, select EIA-485.