Datasheet
- BE-3011/A1 Page 2 -
Ratings:
rated operational voltage (Ue) : 500 V
rated insulation voltage (Ui) : 500 V
rated impulse withstand voltage (Uimp) : 4 kV
conventional free air thermal current (Ith) : 6 A
rated frequency : 50 / 60 Hz
utilization category : AC-15
rated conditional short-circuit current : 1 kA
backup protection : fuse
degree of protection : IP 20
pollution degree : 2
suitability for isolation : No
Further Data:
The EH04-xx auxiliary switches are designed for side mounting to the ESB24, ESB40 or ESB63 contactors.
They have to sets contacts operated by the ESB device.
There are two variants available, EH04-20 with 2 NO contacts and EH04-11 with one NO and one NC contact.
Utilization Category
Ue (V) Ie (A)
NC NO
AC-15 120V 6 A 6 A
240V 4 A 4 A
415V 1 A 3 A
500V 1 A 2 A