Brochure

RCD Type F | 17
F200 Type F DS201 M Type F DDA200 Type F
Standards
IEC/EN 61008, IEC/EN 62423 2
nd
ed IEC/EN 61009, IEC/EN 62423 2
nd
ed IEC/EN 61009 App.G, IEC/EN 62423 2
nd
ed
Electrical features Type
F
Number of poles
2 P, 4 P 1P+N 2P
Rated current I
n
25, 40, 63 A 6 ≤ In ≤ 40 A 40, 63 A
(1)
(to mount with MCB with In = 0,5…63A)
Rated sensitivity I
∆n
0.03 A
Rated voltage U
e
2P: 230 V - 4P: 400 V 230 V 230 V
Insulation voltage U
i
500 V
Max. / Min. operating voltage of circuit test
254 V / 170 V
Rated frequency
50…60 Hz
Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn
- 10000 A same as coupled MCB
Rated breaking capacity acc. to IEC/EN 60947-2 1P+N @230 VAC ultimate Icu
- 10 k A same as coupled MCB
service Ics
- 7.5 k A same as coupled MCB
Rated residual breaking capacity I
∆m
1 kA 6 kA same as coupled MCB
Rated conditional short-circuit current Inc=I
∆c
SCPD - fuse gG 100 A
10kA - -
Rated impulse withstand voltage (1.2/50) U
imp
4 kV
Dielectric test voltage at ind. freq. for 1 min.
2.5 kV
Thermomagnetic release characteristic B: 3 In ≤ Im ≤ 5 In
-
n
same as coupled MCB
C: 5 In ≤ Im ≤ 10 In
-
n
same as coupled MCB
Surge current resistance (wave 8/20)
3000 A
Mechanical features Toggle
blue sealable in ON-OFF position black sealable in ON-OFF position blue sealable in ON-OFF position
Flag indicators contact position indicator (green/red)
yes yes On MCB
differential trip indicator lever position yes Indication with levers position:
- Both MCB/RCD block down: RCD tripping
- MCB down, RCD block up: MCB tripping
Electrical life
10000 cycles
Mechanical life
20000 cycles
Protection degree housing
IP4X
terminal
IP2X
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30
28 cycles with 55°C/90-96% and 25°C/95-100% [°C/RH]
Reference temperature for setting of thermal element
- 30 °C -
Ambient temperature (with daily average ≤ +35 °C)
-25…+55 °C
Storage temperature
-40…+70 °C
Installation Terminal type failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) Top: failsafe bi-directional cylinder-lift terminal
(shock protected)
Bottom: failsafe cylinder-lift terminal (shock protected)
Terminal size top/bottom for cables
25/25 mm
2
Terminal size top/bottom for busbar
10/10 mm
2
10/- mm
2
Tightening torque top/bottom
2.8 Nm
Tool
2 Pozidriv
Mounting
on DIN rail EN 60715 (35 mm) by means of fast clip device
Connection
from top and bottom
Dimensions and weight Dimensions (H x D x W)
2P: 85 x 69 x 35 mm; 4P: 85 x 69 x 70 mm 1P+N: 85 x 67 x 35 mm 2P: 93 x 69 x 69,5 mm
Weight
2P: 225 g; 4P: 375 g 1P+N: 240 g 2P: 180 g
Combination with auxiliary elements Combinable with:
auxiliary contact, signal contact, shunt trip, undervoltage release (see next pages)