RCD Type F Residual current protection for single phase inverters applications
Type F: a new RCD type to ensure complete safety ABB introduces the Type F Residual Current Devices, dedicated to the protection of lines supplying single phase inverters. Nowadays electric appliances including single phase inverters are widely used in household and commercial/industrial applications to reach higher level of efficiency reducing the energy consumption of the electric motors. Single phase inverters regulate the speed of motors by supplying a variable frequency, from 10 to 1000 Hz.
F202 Type F, RCCB in two poles F204 Type F, RCCB in four poles DS201 Type F, compact RCBO DDA 202 Type F, RCD blocks with rated current 25-40-63A and with rated current 25-40-63A 1P+N with rated current 6…40A, (to be mounted with S202 MCBs) sensitivity 30mA for the protection and sensitivity 30mA for the B/C curves and breaking capacity in two poles with rated current of single phase circuits. protection of more than one single 10kA in only two modules.
Residual Current Devices A world of solutions The variety of residual current devices has continuously increased in last decades following the technology evolution and the massive introduction of electronics in all fields of applications.
Type Selection Guide Quick selection of RCD type Typical applications General applications (household, commercial, industrial) Industrial applications Typical loads RCD selection Oven, lights Type AC Dimmer, primary switch mode power supply, multi-speed motors, fan, oven, air conditioning supplied at 50/60Hz with part of the sinus wave Type A Extended lighting circuits, computers supply and other lines subject to unwanted tripping Type A-APR Household appliances and motors with single phase inve
Type F - Protection of lines including loads with single phase inverters Nowadays single phase inverters are present in many household and industrial loads, such as washing machines, hoovers, dishwashers, ventilation, pumps etc…. Inverter technology is a “plus” in domestic equipment, since it helps to reach better performance reducing power consumption and improving energy efficency.
RCD Type F | 7
Maximum protection, in all cases Example of correct design of RCD protection in an industrial application According to the type of loads to be protected , the level of safety and the continuity of service, all different RCDs types could be needed. Pure resistive loads can be protected by means of RCBOs Type AC or A. In case of critical circuits due to a high level of peak leakage current like computers networks or ballasts, RCCBs Type A APR offer the adequate solution.
RCCB F type F type RCD block + MCB B type RCCB MCBs Three-phase frequency converter Cooling system (including single phase inverter) Cooling system (including single phase inverter) ABB asynchronous motor RCD Type F | 9
RCCB F200 type F. The details make the difference A range designed to ensure efficiency and protection Two terminals are available for cables or busbars. Test pushbutton to verify the correct functioning of the device. Information on the device are laser printed to make them clearly visible and long lasting. Bi-directional cylindrical terminal ensure higher safety of connecting operations, making them easier.
RCCBs F200 can be used in ambient conditions where the temperature of the surrounding atmosphere has values between -25°C (snowflake laser printed on the front of the device) and +55°C. The availability of two terminals offers different connection solutions thanks to the possibility to connect two indipendent cables in the same device: the second terminal can be used for an auxiliary circuit or for the supply of devices with small section cables without connecting them together with the main circuit.
RCBO DS201 type F. The details make the difference A range designed to ensure efficiency and protection Contact position indicator (CPI): red - closed contacts; green - open contacts. Bi-directional cylindrical terminal ensure higher safety of connecting operations, making them easier. Information on the device are laser printed to ensure readability over time (including product code). The label carrier to clearly identify the protected circuit.
Any earth fault can be immediately identified through the blue indicator, that signals the differential tripping and which cannot be activated in case of manual operation on the toggle. This prevents any misinterpretations of the device and system status. The terminals available on DS201 make easier the supply operation in parallel with busbars as they are composed by two different seats, a front seat for 25 mm 2 cables and a back seat for 10 mm 2 busbars.
DDA 200 type F - The details make the difference A range designed to ensure efficiency and protection Test pushbutton to verify the correct functioning of the device RCD tripping indicator: Blue lever goes down in case of RCD tripping Laser-marked order code on the front to make easier future orders. Information on the device is laser printed to make it clearly visible and long lasting. DDA200 RCD block mounted with S200 MCB.
Flexibility DDA200 is suitable for mounting with S200 extensive range of MCBs, covering applications in 2P up to 63A with breaking capacity up to 25kA. RCD block DDA200 can be used in ambient conditions where the temperature of the surrounding atmosphere has values between -25°C (snowflake laser printed on the front of the device) and +55°C. Possibility to connect a remote test button for 63A versions.
Range Technical features Standards Electrical features Type Number of poles Rated current In Rated sensitivity I ∆n Rated voltage U e Insulation voltage U i Max. / Min. operating voltage of circuit test Rated frequency Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn Rated breaking capacity acc.
F200 Type F DS201 M Type F DDA200 Type F IEC/EN 61008, IEC/EN 62423 2nd ed IEC/EN 61009, IEC/EN 62423 2nd ed IEC/EN 61009 App.G, IEC/EN 62423 2nd ed 2P, 4P 1P+N 2P 25, 40, 63 A 6 ≤ In ≤ 40 A 40, 63 A (1) (to mount with MCB with In = 0,5…63A) F 0.03 A 2P: 230 V - 4P: 400 V 230 V 230 V 500 V 254 V / 170 V 50…60 Hz - 10000 A - 10 kA same as coupled MCB same as coupled MCB - 7.5 kA same as coupled MCB 1 kA 6 kA same as coupled MCB 10kA - - 4 kV 2.
Type F codes Number of poles Rated residual current I∆n mA Rated current In A EAN 8012542 Order details Type code Order code Weight 1 piece kg Pack unit pc. RCCB F200 2CSC423001F0901 2 30 4 25 992738 F202 F-25/0,03 2CSF202325R1250 0.225 1/6 40 992837 F202 F-40/0,03 2CSF202325R1400 0.225 1/6 63 992936 F202 F-63/0,03 2CSF202325R1630 0.225 1/6 25 993032 F204 F-25/0,03 2CSF204325R1250 0.375 1/3 40 993131 F204 F-40/0,03 2CSF204325R1400 0.
Accessories DDA 202 ST or UR or OR H H Combination of auxiliary elements with F 200 H Auxiliary contact S2C-H6R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP AR Auto reclosing unit F2C-ARI / F2C-ARH MOD-F Motor operating device F2C-CM ST-F Shunt trip for F 200 RCCB F2C-A BP H H or S/H S/H (H) H ST-F or UR or OR F 200 AR/MOD-F F2 125 H or S/H S/H (H
Accessories Combination of auxiliary elements with DS201 H Auxiliary contact S2C-H6R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP MOD-DS Motor operating device DS2C-CM ST-F Shunt trip for F 200 RCCB F2C-A + S/H + H + MOD-DS + S/H + S/H (H) DS201 +H+H + ST-F + H + H + ST-F + S/H + S/H (H) + UR + H + H + OR + H + H + UR + S/H + S/H (H) + OR + S/H + S/H (H)
Combination of auxiliary elements with DDA200 H Auxiliary contact S2C-H6R H-R Auxiliary contact S2C-H6-...R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R ST Shunt trip for S 200 MCB S2C-A...
Accessories 2CSC423005F0901 Auxiliary contact Weight 1 piece [kg] Pack unit pc. Bbn Order details 4016779 Type code EAN Order code Change-over 1CO 563826 S2C-H6R 2CDS200912R0001 0.
2CSC423009F0901 Auto-reclosing units Order code Weight 1 piece [kg] Pack unit pc. F2C-ARI 2CSF200996R0013 0.166 1 Home automatic resetting unit (30 mA) 732433 F2C-ARH 2CSF200992R0005 0.200 1 Home automatic resetting unit (30 mA) 733232 with RCCB autotest F2C-ARH-T 2CSF200991R0005 0.200 1 Bbn Order details 8012542 Type code EAN Order code Weight 1 piece [kg] Pack unit pc. 026556 F2C-CM 2CSF200997R0013 0.166 1 135951 DS2C-CM 2CSR201997R0013 0.
Overall dimensions F 202 F 204 85 45 F204 85 F202 6,8 17,5 17,5 35 17,5 70 17,5 44 DDA 202 69 85 93 45 85 DS201 9,7 17,5 35 43 58 67 73 DDA 202 17,5 35 45 85 93 DDA 202 9,7 17,5 17,5 35 Dimensions in mm 24 | RCD Type F 8,75 34,5 6,8 44 69 8,75 34,5
FAQ - Frequently Ask Questions Is it possible to realize selectivity with type F RCDs? What about the coordination with MCBs? The coordination and selectivity rules are common for Type AC, A, A-APR and F RCDs. For an RCD type F, the first level of selectivity can be realized with any RCD in selective version. Selectivity is guaranteed thanks to the time delay and higher sensitivity of the RCD upstream. For any detail regarding the coordination, please refer to the System pro M compact®.
| RCD Type F
RCD Type F | 27
ABB SACE A division of ABB S.p.A. Modular Devices Viale dell’Industria, 18 20010 Vittuone (MI) - Italy Tel.: +39 02 9034 1 Fax: +39 02 9034 7609 www.abb.it/lowvoltage www.abb.com The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice. Copyright 2014 ABB. All rights reserved.