Cut Sheet

terminals delivered open. The -M, -N, -E and -U versions offer different
markings to match the existing marking on the contactor or the contactor relay
it is mounted on (see "Terminal marking and positioning" data in the catalogue).
2 NO, 2 NC Mounted Auxiliary
Contacts
Front mounting Mounting Type
2 Number of Auxiliary
Contacts NC
2 Number of Auxiliary
Contacts NO
K Object Classification Code
1 piece Order Multiple
Accessories for Block Contactors Product Main Type
Auxiliary Contact Block Product Name
Auxiliary Circuit 50 / 60 Hz Rated Frequency (f)
6 kV Rated Impulse Withstand
Voltage (U
imp
)
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Insulation Voltage
(U
i
)
(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current
AC-15 (I
e
)
(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Current
DC-13 (I
e
)
Auxiliary Circuit 24 ... 690 V
Rated Operational Voltage
for 0.1 s 140 A
for 1 s 100 A
Rated Short-time
Withstand Current (I
cw
)
20171115 RoHS Date
AF09
AF12
AF16
Suitable For
Screw Terminals Terminal Type
Auxiliary Circuit 1.2 N·m Tightening Torque
Auxiliary Circuit 10 mm Wire Stripping Length
Certificates and Declarations (Document Number)
ABS_15-GE1349500-PDA_90682247 ABS Certificate
BV_2634H24900B0 BV Certificate
CB_SE-93053 CB Certificate
CCC_2013010304651497 CCC Certificate
CQC2011010304496319
CQC2013010304651497
CQC Certificate
UL_20180227_E252354_3_1 cUL Certificate
2020980304001258 Declaration of Conformity
3