240 piece Package Level 3 Units
ABS_15-GE1349500-PDA_90682247 ABS Certificate
BV_2634H36994A BV Certificate
CB_SE_77418 CB Certificate
CCC_2012010304589737
CCC_2015010304824714
CCC Certificate
1SBD250000U1000 Declaration of Conformity - CE
DNV-GL_TAE00001AF-3 DNV Certificate
DNV-GL_TAE00001AF-3 DNV GL Certificate
EAC_RU C-FR ME77 B03597 EAC Certificate
1SBD250168E1000 Environmental Information
DNV-GL_TAE00001AF-3 GL Certificate
1SBC101036M6801 Instructions and Manuals
KC_HW02016-15010A KC Certificate
LRS_1300087E1 LR Certificate
RINA_ELE084013XG RINA Certificate
RMRS_1802705280 RMRS Certificate
1SBD250000U1000 RoHS Information
UL_20130926-E312527_14_1 UL Certificate
UL_E312527 UL Listing Card
Certificates and Declarations (Document Number)
—
(600 V AC) 80 A General Use Rating UL/CSA
(220 ... 240 V AC) Three Phase 20 hp
(440 ... 480 V AC) Three Phase 40 hp
(550 ... 600 V AC) Three Phase 50 hp
(120 V AC) Single Phase 3 hp
(200 ... 208 V AC) Three Phase 15 hp
(240 V AC) Single Phase 10 hp
Horsepower Rating UL/CSA
Auxiliary Circuit 11 IA
Control Circuit 11 IA
Main Circuit 35 IA
Tightening Torque UL/CSA
Technical UL/CSA
—
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Ambient Air Temperature
Category B according to IEC 60947-1 Annex Q Climatic Withstand
3000 m Maximum Operating Altitude Permissible
5 ... 300 Hz 3 g closed position / 3 g open position Resistance to Vibrations acc. to IEC 60068-2-6
Closed, Shock Direction: A 25 K40
Closed, Shock Direction: B1 25 K40
Closed, Shock Direction: B2 15 K40
Closed, Shock Direction: C1 25 K40
Closed, Shock Direction: C2 25 K40
Open, Shock Direction: B1 5 K40
Resistance to Shock acc. to IEC 60068-2-27
Following EU Directive 2011/65/EU RoHS Status
Environmental
—
—