User`s manual

59
FLN Protocol Technical Data
69 FLN LOC REF Commanded by FLN to temporarily “steal” input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
70 DI 1 ACTUAL Indicates the status of Digital Input 1 (1 = ON, 0 = OFF). 0118, bit 2
71 DI 2 ACTUAL Indicates the status of Digital Input 2 (1 = ON, 0 = OFF). 0118, bit 1
72 DI 3 ACTUAL Indicates the status of Digital Input 3 (1 = ON, 0 = OFF). 0118, bit 0
73 DI 4 ACTUAL Indicates the status of Digital Input 4 (1 = ON, 0 = OFF). 0119, bit 2
74 DI 5 ACTUAL Indicates the status of Digital Input 5 (1 = ON, 0 = OFF). 0119, bit 1
75 DI 6 ACTUAL Indicates the status of Digital Input 6 (1 = ON, 0 = OFF). 0119, bit 0
76 RO 1 ACTUAL Indicates the status of Relay Output 1 (1 = ON, 0 = OFF). 0122, bit 2
77 RO 2 ACTUAL Indicates the status of Relay Output 2 (1 = ON, 0 = OFF). 0122, bit 1
78 RO 3 ACTUAL Indicates the status of Relay Output 3 (1 = ON, 0 = OFF). 0122, bit 0
79 RO 4 ACTUAL Indicates the status of Relay Output 4 (1 = ON, 0 = OFF). 0123, bit 2
80 RO 5 ACTUAL Indicates the status of Relay Output 5 (1 = ON, 0 = OFF). 0123, bit 1
81 RO 6 ACTUAL Indicates the status of Relay Output 6 (1 = ON, 0 = OFF). 0123, bit 0
82 AI 1 ACTUAL Indicates the input level of Analog Input 1. 0120
83 AI 2 ACTUAL Indicates the input level of Analog Input 2. 0121
84 AO 1 ACTUAL Indicates the output level of Analog Output 1. 0124
85 AO 2 ACTUAL Indicates the output level of Analog Output 2. 0125
86 OK.ALARM Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
87 OK.MAINT Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
88 ALARM WORD1 This point is a bit-field indicating active alarms in the drive. 0308
89 ALARM WORD2 This point is a bit-field indicating active alarms in the drive. 0309
90 LAST FAULT This point is first in the drive's fault log and indicates the most
recent fault declared.
0401
91 PREV FAULT 1 This point is second in the drive's fault log and indicates the
previous fault declared.
0412
92 PREV FAULT 2 This point is last in the drive's fault log and indicates the
oldest fault in the log.
0413
93 OK.FAULT Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
FLN Detailed Point Descriptions
Point Description
Drive
Parameter