FLN Protocol Technical Data
50 PRC PID GAIN Sets the proportional gain of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
51 PRC PID ITIM Sets the integration time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4002 (SET1)
4102 (SET2)
52 PRC PID DTIM Sets the derivation time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
4001 (SET1)
4101 (SET2)
53 PRC PID DFIL Sets the time constant for the error-derivative of the active
Process PID set, as selected by Point 54, PRC PID SEL
(1 = SET2, 0 = SET1).
4004 (SET1)
4104 (SET2)
54 PRC PID SEL Selects the active Process PID set (1 = SET2, 0 = SET1). 4027
55 EXT PID GAIN Sets the proportional gain of the External PID controller. 4201
56 EXT PID ITIM Sets the integration time of the External PID controller. 4202
57 EXT PID DTIM Sets the derivation time of the External PID controller. 4203
58 EXT PID DFIL Sets the time constant for the error-derivative of the External
PID controller.
4204
59 LOCK PANEL Command by FLN to lock the panel and prevent parameter
changes (1 = LOCK, 0 = UNLOCK).
1602
60 INPUT REF 1 Sets Input Reference 1.
Parameter 1102 must be set to COMM for FLN to control this
value.
61 INPUT REF 2 Sets Input Reference 2.
Parameter 1106 must be set to COMM for FLN to control this
value.
62 EXT PID STPT The setpoint for the External PID controller.
The function of this point requires parameter 4210, PID
Setpoint Select, to be set to 19 (Internal).
4211
63 EXT PID FBCK The External PID feedback signal. 0131
64 EXT PID DEV The deviation of the External PID output signal from its
setpoint.
0133
65 N/A
66 SPD OUT MIN Sets the minimum output speed of the drive as a percentage
of the motor nominal rating.
2007
(SCALAR)
2001
(SPEED)
67 SPD OUT MAX Sets the maximum output speed of the drive as a percentage
of the motor nominal rating.
2008
(SCALAR)
2002
(SPEED)
68 FLN LOC CTL Commanded by FLN to temporarily “steal” start/stop control
of the drive from its normal source and place it under FLN
control. This functionality is analogous to placing the drive in
HAND mode at the panel, with the control being taken by
FLN instead. HAND mode at the panel has priority over this
point. Thus, this point is only effective in temporarily taking
control from the digital inputs or some other internal control
functionality.
FLN Detailed Point Descriptions
Point Description
Drive
Parameter