FLN Protocol Technical Data
Process PID
External PID
Scaling Drive Feedback Values
Feedback values are provided with units of percent, where 0% and 100%
correspond to the range of the sensor being used to measure the control variable.
These points have default units in Hz. If other units are required:
Unbundle these points with appropriate slopes and intercepts.
The new intercept equals the lowest value of the desired range.
FLN Process PID Report
Point
Subpoint Name Data
#Type
15 LAI PRC PID FBCK Each host FLN application (e.g. CIS or Insight) controls
both the particular data reported for each point, and the
report format.
16 LAI PRC PID DEV
50 LAO PRC PID GAIN
51 LAO PRC PID ITIM
52 LAO PRC PID DTIM
53 LAO PRC PID DFIL
54 LDO PRC PID SEL
60 LAO INPUT REF1
61 LAO INPUT REF2
82 LAI AI 1 ACTUAL
83 LAI AI 2 ACTUAL
84 LAI AO 1 ACTUAL
85 LAI AO 2 ACTUAL
FLN External PID Report
Point
Subpoint Name Data
#Type
55 LAO EXT PID GAIN Each host FLN application (e.g. CIS or Insight) controls
both the particular data reported for each point, and the
report format.
56 LAO EXT PID ITIM
57 LAO EXT PID DTIM
58 LAO EXT PID DFIL
62 LAO EXT PID STPT
63 LAI EXT PID FBCK
64 LAI EXT PID DEV
82 LAI AI 1 ACTUAL
83 LAI AI 2 ACTUAL
84 LAI AO 1 ACTUAL
85 LAI AO 2 ACTUAL