Installation Manual

Technical data
50
10.11
General logic interface specifications
Parameter Specification
Connectivity Mobile communication with Nano-SIM
socket type M2M (Machine To Machine)
2G (GSM)
3G (WCDMA)
4G (LTE)
Smart meter communication
Modbus RTU (RS485)
Modus TCP/IP
Ethernet
1x 10/100 BaseT, RJ45 Socket
Extra ethernet (daisy chain)
1x 10/100 BaseT, RJ45 Socket
WiFi (WAN) IEEE 802.11 b/g/n, 2.4 GHz
Bluetooth BLE 5.0
RFID MIFARE ISO/IEC 14443A RFID cards
Compatible mobile device operating sys-
tems
Android 4.4 or higher
iOS8 or higher
10.12
Cable specifications
10.12.1
AC input cable
Parameter Specification
EV charger station connection type Terminal /lugs and screws
Wire size for the terminal (PE) 8 AWG
Wire size for the terminal (
L1,L2)
2 AWG
Strip length 14 mm(L1,L2)/8.5mm(PE)
Cable shielding (optional) The local rules require shielded cables.
The cable shielding must be connected
to the PE rail at the two ends of the ca-
ble.
Diameter of the phase conductors Refer to the local rules.
Diameter of the PE conductor The same as te diameter of the phase
conductors
Consult your local electrical codes for the correct wire size, based on the envi-
ronment, the conductor type and the rating of the EVSE.
The wire AWG is based on the copper wire type.