Installation Manual

Technical data
49
Z1
A
Z2
10.9.2
Space requirements for installation
A EVSE
Parameter
Specification [mm]
Specification [inches]
Z1
> 200
> 8
Z2 (indoor use)
450 to 1200
18 to 48
Z2 (outdoor use)
600 to 1200
24 to 48
10.10 AC input specifications
10.10.1
General specifications
Parameter Specification
Frequency 50 Hz or 60 Hz
Overvoltage category Category III
Protection Overcurrent
Overvoltage
Undervoltage
Earth fault, including DC leakage protec-
tion
5
Integrated surge protection
10.10.2
AC input specifications
Parameter Specification
Input AC power connection 240 V AC
Earth (ground) fault protection internal 20 mA AC CCID