All Specifications are Per Charging Station or Port
Max. Output
(Charging)
Current
Typical Circuit
Breaker (CB)
3
Typical Wire Specs
Typical
Conduit
Size
Notes / Assumptions
12A
15A
Two #12AWG Wires (Line)
One #12AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
16A
20A
Two #10AWG Wires (Line)
One #12AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
24A
30A
Two #8AWG Wires (Line)
One #10AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
32A
40A
Two #8AWG Wires (Line)
One #10AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
40A
50A
Two #6AWG Wires (Line)
One #8AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
64A
80A
Two #4AWG Wires (Line)
One #8AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
72A
90A
Two #3AWG Wires (Line)
One #8AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop
80A
100A
Two #2AWG Wires (Line)
One #8AWG Wire (Ground)
1"
150FT. One-Way Distance.
≤3% Voltage Drop