Opal Pro to Mod TCP Opal Pro MS6 SERIES AB Ethernet IP Interface Users Manual Revision 1.
Opal Pro to Mod TCP Page 2
Opal Pro to Mod TCP FOR YOUR SAFETY Only qualified personnel should install this equipment, after first reading and understanding all the information in this manual. All instructions should be strictly adhered to. The user should consult Brock Solutions or a SAF OPAL Starters supplier for clarification of the contents of this manual should any doubt or questions arise. The installation of this equipment must be conducted in accordance with all national, regional and local electrical codes.
Opal Pro to Mod TCP Page 4
Opal Pro to Mod TCP Table of Contents INTRODUCTION .............................................................................................. 6 HARDWARE .................................................................................................... 6 JUMPER SETTINGS........................................................................................ 6 LED INDICATORS ........................................................................................... 7 OPAL PRO PARAMETER SETTINGS ........
Opal Pro to Mod TCP Opal Pro to Mod TCP Introduction The Opal Pro can be monitored and controlled over an Ethernet communication network using the AB Ethernet IP protocol. The Opal Pro connects to the Ethernet network through and optional Ethernet card that is mounted on the main Opal Pro control card (CA530). Access is gained to the Ethernet card via the communication opening on the right side of the Opal Pro.
Opal Pro to Mod TCP LED Indicators Two bi-colour (red/green) LED indicators are mounted beside the network connector. The upper LED indicates the Ethernet interface card status.
Opal Pro to Mod TCP Opal Pro Parameter Settings The parameters in the Opal Pro used to configure the Ehernet interface card (group 14) are only accessible if a Ethernet interface card is installed. The parameter settings are as follows: Opal Pro Setting Description Parameter 2.02 Comm Module Ethernet Type of interface card installed (read only) 10.01 Start/Stop Comm This allows the Opal Pro to be Module started and stopped over the communication link 10.
Opal Pro to Mod TCP 15.04 Comm Fault Enable Disable 15.05 Comm Fault Time 0.1 to 5.0 secs Enable – Opal Pro trips out on a communication fault Disable – Nothing happens on a communication fault This is the time setting that the Opal Pro uses to detect a communication fault. Bit 15 of the command word must change state twice with in the time set in this parameter.
Opal Pro to Mod TCP I/O Configuration The Opal Pro supports 4 input words and 51 output words.
Opal Pro to Mod TCP Output Words (Polled) Word 1 AB Ethernet IP Name Description Input Word 0 Status Word 2 Input Word 1 Word 3 Input Word 2 Parameter 1.01 1.02 AB Ethernet IP Input Word 3 Input Word 4 Current Feedback Phase Angle Actual Name Bit 0 – Ready to Run (drive is enable and has 3 phase power) Bit 1 –Running (start is regulating) Bit 2 – Full On (starter is phased fully on) Bit 3 – Up to Speed (started is phased fully on and the current is below 105% of nameplate current as set in 13.
Opal Pro to Mod TCP 1.07 Input Word 9 1.08 Input Word 10 Input Word 11 Input Word 12 Input Word 13 Input Word 14 2.01 2.02 2.03 10.
Opal Pro to Mod TCP 12.01 Input Word 27 13.01 Input Word 28 Input Word 29 Input Word 30 Input Word 31- Input Word 36 Input Word 37 Input Word 38 Input Word 39 Input Word 40 Input Word 41 Input Word 42 Input Word 43 Input Word 44 Input Word 45 Input Word 46 Input Word 47 13.02 13.03 14.01-14.06 14.07 14.08 14.09 14.10 14.11 14.12 14.13 14.14 14.15 15.01 15.02 15.03 15.04 15.
Opal Pro to Mod TCP NOTE: The Opal Pro must have firmware version 1.70 or higher.