41 10-SLOT RACK W/ COMMUNICATION CARDS ➤1 ➤2 PROGRAMMING AND OI SOFTWARE 42 43 1746 I/O MODULES ➤3 44 45 7-SLOT RACK W/ 5/05 ETHERNET® PROCESSOR ➤4 System Overview SLC 500™ Programmable Controllers & I/O Modules (Bulletins 1746 and 1747)
SLC 500 Processors: The Compact Controllers for Big Applications Don’t be fooled by the SLC 500 size. From Take Control food processing to steel fabrication, you won’t find a more versatile or powerful solution for stand-alone or distributed Experience Complete Satisfaction With Allen-Bradley industrial control assignments. reputation as the most trusted brand Capacity to Do More. Flexibility to Cost Less. name in industrial automation.
from the plant floor to Device-Level Control management information Connectivity to the popular 1747-SDN systems. Through Ethernet DeviceNet™ Scanner module gives you a networks, the SLC 500 single-cable interface to “smart” devices, can communicate plant-floor including sensors, push buttons, motor data in data acquisition, starters, simple operator interfaces, supervisory control, and drives.
SLC 500 Programmable Controllers and I/O Modules Table of Contents SLC 500 Family .................................................................................................. 5 SLC 500 Modular Processors ............................................................................ 7 Discrete I/O Modules ...................................................................................... 13 4 Analog I/O Modules .......................................................................................
SLC 500 Programmable Controllers and I/O Modules SLC 500 Family The Allen-Bradley SLC 500 is Rockwell Automation’s small chassis-based, modular family of programmable controllers (PLC’s) and chassis-based I/O. It consists of 5 processors, I/O and peripheral devices.
SLC 500 Programmable Controllers and I/O Modules SLC 500 Common Specifications The following specifications apply to all SLC 500 modular components unless noted. 6 Description Specification Temperature Operating: 0˚C to +60˚C (+32˚F to +140˚F) Storage: -40˚C to +85˚C (-40˚F to +185˚F) Humidity 5 to 95% without condensation Vibration Operating: 1.0G at 5 to 2000 Hz Non-operating: 2.5Gs at 5 to 2000 Hz Shock Operating: (all modules except relay contact) 30.
SLC 500 Programmable Controllers and I/O Modules SLC 500 Modular Processors The SLC 500 processors offer a wide range of choices in memory, I/O capacity, instruction 7 set, and communication ports to allow you to tailor your control system to exactly meet your application requirements.
SLC 500 Programmable Controllers and I/O Modules SLC 5/02 Processors (Catalog No. 1747-L524) The SLC 5/02 processor offers additional instructions, increased diagnostics, faster throughput, and additional peer-to-peer communication options; building on what the SLC 5/01 processors offer.
SLC 500 Programmable Controllers and I/O Modules SLC 5/04 Processors (Catalog No. 1747-L541, -L542, or -L543) The SLC 5/04 processor provides the baseline functionality of the SLC 5/03processor plus DH+ communication. Communication via DH+ is 3 to 12 times faster than DH-485, providing you with increased performance levels. In addition, the SLC 5/04 processor runs approximately 15% faster than the SLC 5/03 processor.
SLC 500 Programmable Controllers and I/O Modules SLC 5/05 Processors (Catalog No. 1747-L551, -L552, or -L553) The SLC 5/05 processor provides identical control functionality as the SLC 5/04 processor using standard Ethernet communications instead of DH+. Ethernet communication takes place at 10 Mbps, providing you with a high-performance network for program upload/download, on-line editing, peer-to-peer messaging, data 10 acquisition, and operator interface (e.g. RSView32).
SLC 500 Programmable Controllers and I/O Modules Processor Capabilities The following table summarizes the specifications for the SLC 500 modular processors. Specification Memory Size (words) SLC 5/01 L511: 1K L514: 4K SLC 5/02 L524: 4K SLC 5/03 L531: 8K L532: 16K SLC 5/04 L541: 16K L542: 32K L543: 64K Power Supply Loading 350 mA at 5V dc 350 mA at 5V dc 500 mA at 5V dc 1.
SLC 500 Programmable Controllers and I/O Modules Memory Modules The following table summarizes the available memory back up options for the SLC 500 processors. EEPROM memory modules provide non-volatile memory back-up. Flash EPROMs (Flash Erasable Programmable Read Only Memory) combine the versatility of EEPROMs with the security of UVPROMs.
SLC 500 Programmable Controllers and I/O Modules Discrete I/O Modules Our wide variety of input, output, and combination modules makes the SLC 13 500™ family the smart choice for all of your small PLC applications. I/O modules are available in a wide variety of densities including 4-, 8-, 16-, and 32-point and can interface to AC, DC, and TTL voltage levels.
SLC 500 Programmable Controllers and I/O Modules Discrete Input Modules 14 Catalog Number Module Description 1746-IA4 AC Voltage Category Number of Inputs Points Per Power Supply Common Loading 5V dc 24V dc 100/120V ac 4 4 35 mA 0 mA 1746-IA8 100/120V ac 8 8 50 mA 0 mA 1746-IA16 100/120V ac 16 16 85 mA 0 mA 1746-IM4 200/240V ac 4 4 35 mA 0 mA 1746-IM8 200/240V ac 8 8 50 mA 0 mA 1746-IM16 200/240V ac 16 16 85 mA 0 mA 1746-IN16 AC/DC 24V ac/V dc 16 16 85 mA 0
SLC 500 Programmable Controllers and I/O Modules Discrete Output Modules 15 Catalog Number Module Description Voltage Category Number of Outputs Points Per Continuous Power Supply Common Current per Loading Point at 30˚C (max.)ª1) 5V dc 24V dc 1746-OA8 AC 120/240V ac 8 4 1A 185 mA 0 mA 120/240V ac 16 8 0.50A 370 mA 0 mA 1746-OA16 1746-OAP12 High Current AC (short-circuit fuse protection) 120/240V ac 12 6 2.
SLC 500 Programmable Controllers and I/O Modules Combination Discrete Input and Output Modules 16 Catalog Number Module Description Voltage Category Number of Points Points Per Common Power Supply Loading 5V dc 24V dc 1746-IO4 AC Input 120V ac 2 inputs AC/DC Relay Output 5 to 265V ac 5 to 125V dc 2 outputs 120V ac 4 inputs 5 to 265V ac 5 to 125V dc 4 outputs 120V ac 6 inputs 5 to 265V ac 5 to 125V dc 6 outputs DC Input 24 V dc 6 inputs AC/DC Relay Output 5 to 265V ac 5 to 125V dc
SLC 500 Programmable Controllers and I/O Modules I/O Wiring Terminals on the 4-, 8-, 12- and 16-point modules have self-lifting pressure plates that accept two 14 AWG (2mm2) wires. All 16-point I/O modules, 1746-OX8, -OB6EI, -OBP8, -OAP12, -IO12 and IO12DC are equipped with color-coded removable terminal blocks. 17 32-point I/O modules are equipped with a 40-pin, MIL-C-83503 type header and a removable wiring connector (1746-N3). The connector can be assembled with the wire type and length of your choice.
SLC 500 Programmable Controllers and I/O Modules Analog I/O Modules Small programmable controllers continue to be placed in process 18 control applications demanding high densities, faster, more accurate measurement, and the flexibility to interface to a variety of temperature, pressure, and flow transducers. The SLC 500 family offers multiple choices that broaden its control capabilities to serve these and other demanding applications.
SLC 500 Programmable Controllers and I/O Modules Analog Input Modules Input Selection Chart Catalog Number Input Channels per Module Backplane Current Draw 19 5V dc 24V dc 1746-NI4 4 differential, voltage or current selectable 25 mA 85 mA 1746-NI8 8 differential, voltage or current selectable 200 mA 100 mA 1746-NI16I 16 single-ended, current 125 mA 75 mA 1746-NI16V 16 single-ended, voltage 125 mA 75 mA Analog Output Modules Output Selection Guide Catalog Number Output Channels per Mod
SLC 500 Programmable Controllers and I/O Modules Input Characteristics 20 Specification NI4 NI8 NIO4I NIO4V FIO4V FIO4V NI16I NI16V (Current only) (Voltage only) Number of inputs 4 8 2 2 2 2 16 Current/Voltage ranges 16 ±10V dc ±20 mA (+10 to -10V dc (0 to 20 mA; 0 to 5V dc; 4 to 20 mA; 1 to 5 V dc) 0 to 1 mA Step response 60 ms selectable 60 ms 100 µs selectable Overall Accuracy 0°C to +60°C (+32°F to +140°F) ±0.642% ±0.05% (I) ±0.10% (V) ±0.642% ±0.85% ±0.
SLC 500 Programmable Controllers and I/O Modules Temperature Modules Greatly enhance the temperature monitoring and control capabilities of 21 your SLC 500 system with the 1746 temperature modules. Temperature modules eliminate the need for expensive thermocouple transmitters, providing a more economical means of addressing process applications in industries requiring temperature 1746-NT4, 1746-NT8, 1746-INT4 Thermocouple/mV Modules measurement and control.
SLC 500 Programmable Controllers and I/O Modules Thermocouple Temperature Ranges 22 Thermocouple Input ˚C Temperature Range ˚F Temperature Range Accuracy Max. Error at +25˚C (+77˚F) Type J -210˚C to 760˚C -346˚F to 1400˚F ±1.06˚C (NT4) ±1.4˚C (NT8) ±1.6˚C (INT4) Type K -270˚C to 1370˚C -454˚F to 2498˚F ±1.72˚C (NT4) ±1.5˚C (NT8) ±3.8˚C (INT4) Type T -270˚C to 400˚C -454˚F to 752˚F ±1.43˚C (NT4) ±1.3˚C (NT8) ±2.05˚C (INT4) Type E -270˚C to 1000˚C -454˚F to 1832˚F ±0.72˚C (NT4) ±1.
SLC 500 Programmable Controllers and I/O Modules 1746-NR4 and -NR8 RTD Resistance Input Modules Features These modules provide a choice of four filter frequencies, permitting you to select input noise filtering appropriate to the application and surrounding environment. Either or both 50Hz and 60Hz noise can be filtered from the input signal for greater noise rejection and resolution.
SLC 500 Programmable Controllers and I/O Modules RTD Temperature Range and Accuracy Specifications RTD Type 1746-NR4 1746-NR8 0.5 mA Excitation 24 Platinum 100Ω (385) 2.0 mA Excitation Temp. Range Acc. Temp. Range -200˚C to +850˚C ±1.0˚C -200˚C to +850˚C 0.25 mA Excitation Acc.(1) Temp. Range 1.0 mA Excitation Acc.(1) Temp. Range ±0.5˚C -200˚C to +850˚C ±0.5˚C -200˚C to +850˚C Acc.(1) ±0.7˚C (-328˚F to +1562˚F) (±2.0˚F) (-328˚F to +1562˚F) (±0.9˚F) (-328˚F to +1562˚F) (±0.
SLC 500 Programmable Controllers and I/O Modules Resistance Input Specifications Resistance 0.5 mA Excitation Resistance 2.0 mA Excitation Accuracy(1) Temperature Resistance Range 1746-NR4 150Ω 500Ω 0Ω to 150Ω 0Ω to 500Ω Drift ±0.2Ω ±0.5Ω Resolution Repeatability Accuracy(1) Temperature Range Drift ±0.006Ω/˚C 0Ω to 150Ω ±0.15Ω ±0.004Ω/˚C (±0.003Ω/˚F) (±0.002Ω/˚F) ±0.014Ω/˚C 0Ω to 500Ω ±0.5Ω ±0.014Ω/˚C (±0.008Ω/˚F) 1000Ω 0Ω to 1000Ω ±1.0Ω ±0.029Ω/˚C 0Ω to 3000Ω ±1.5Ω ±0.
SLC 500 Programmable Controllers and I/O Modules 26 Counting, Positioning and Motion Modules The Allen-Bradley SLC 500 counting, positioning, and motion modules are well suited to basic motion control, and offer a wide variety of control application solutions. Whether you have positioning applications, singleaxis or servo control, or high-speed registration, there is an SLC 500 module to meet your needs.
SLC 500 Programmable Controllers and I/O Modules Specifications Description Specification Inputs 1 count input 5V, 12V, or 24V dc Max. Input Frequency 50 KHz for range, 32 KHz for rate, 50 KHz for sequencer Max. Counts 16-bit, ±32,768 Outputs 4 open-collector outputs: 5V, 12V, or 24V dc; Maximum current: 125mA at 30˚C Module Update Time Range Mode: 3.9 ms; Rate Mode: 70 ms + rate; Sequencer Mode: 1.
SLC 500 Programmable Controllers and I/O Modules 1746-HSTP1 Stepper Control Module The 1746-HSTP1 Stepper Control module is a single-axis stepper controller. Operating with a variety of SLC 500 processors, this single-slot module is capable of providing up to 250 KHz pulse train output for micro-stepping applications. 28 Use this module for open-loop stepper applications with single-axis control requirements. The SLC’s data table contains all the program and configuration information.
SLC 500 Programmable Controllers and I/O Modules Features • Four fast I/O points — Controlled by the IMC 110 system, saving valuable throughput time. • +10V dc signal - Provides an interface to most servo drives. • 5 ms Servo Loop Closure Rate - Provides a high degree of accuracy and system response. • Termination Panel Interface - Provides a wiring connection for fast I/O, E-stop, power supplies, drive command and encoder feedback.
SLC 500 Programmable Controllers and I/O Modules Application Specific Modules 30 The SLC 500 family offers a variety of modules for specialty applications which all fit directly into the SLC chassis. 1746-BAS, 1746-BAS-T BASIC Modules The 1746-BAS and 1746-BAS-T modules, which are programmed using the BASIC language, add additional functionality to any SLC 500 application. The BASIC modules can be programmed with the BASIC development software PBASE.
SLC 500 Programmable Controllers and I/O Modules Specifications Specification BAS Memory Size 24K bytes battery backed RAM Optional Memory Modules BAS-T 8K byte and 32K byte EEPROM 8K byte and 32K byte UVPROM Number of Ports 3 Port Configuration RS-232, RS-422, RS-485, DH-485 Backplane Current Draw 150 mA at 5V dc, 40 mA at 24V dc Program Execution Speed N/A 31 4 times faster than BAS 1747-PCI Computer Bus Interface Module/System The 1746-PCI computer bus interface module/system consists o
SLC 500 Programmable Controllers and I/O Modules 1746-BTM Barrel Temperature Module The temperature control module is an intelligent I/O module that can provide a maximum of 4 PID loops for temperature control. The module has 4 analog thermocouple (TC) inputs. Each input functions as the process variable (PV) for a PID loop. The PID algorithm and tuning-assisted-process (TAP) algorithm are performed on the module for each of the loops.
SLC 500 Programmable Controllers and I/O Modules Communication Choices Rockwell Automation offers many control and communication media products that help you integrate plant operations. These products, combined with other vendors’ products, provide plant-wide solutions that meet your control system and business needs.
SLC 500 Programmable Controllers and I/O Modules Ethernet Network The TCP/IP Ethernet network is a local-area network designed for the high-speed exchange of information between computers and related devices. With its high bandwidth (10 Mbps to 100 Mbps), an Ethernet network allows many computers, controllers, and other devices to communicate over vast distances. 34 At the information layer, an Ethernet network provides enterprise-wide systems access to plant-floor data.
SLC 500 Programmable Controllers and I/O Modules 1747-SCNR ControlNet Scanner The 1747-SCNR scanner module provides a scheduled ControlNet network connection for SLC 5/03 and higher processors. With scheduled messaging, the SLC processor can control I/O events in real-time on the ControlNet network.
SLC 500 Programmable Controllers and I/O Modules DeviceNet connectivity for the SLC 500 is provided by the following interfaces: 1747-SDN DeviceNet Scanner Module The 1747-SDN DeviceNet Scanner modules acts as an interface between DeviceNet devices and SLC 36 5/02 or higher processors. The scanner communicates over the DeviceNet network to: • Read inputs and write outputs • Download configuration data • Monitor operational status The scanner communicates with the SLC processor to exchange I/O data.
SLC 500 Programmable Controllers and I/O Modules Data Highway Plus The Data Highway Plus (DH+) network is a local-area network designed to support remote programming and data acquisition for factory-floor applications. You can also use DH+ communication modules to implement a peer-to-peer network. 37 You can use a DH+ network for data transfer to other PLC-5 controllers or high-level computers and as a link for programming multiple PLC-5 controllers.
SLC 500 Programmable Controllers and I/O Modules 1747-AIC Isolated Link Coupler SLC 500 programmable controllers communicate across an embedded DH-485 network for program support and monitoring. The following products provide networking options for the SLC 500 programmable controllers: 1747-PIC Interface Converter, 1747-AIC, and 1761-NET-AIC Advanced Interface Converter. The Isolated Link Coupler provides an electrically isolated network 38 connection for an SLC 500 controller.
SLC 500 Programmable Controllers and I/O Modules Universal Remote I/O connectivity for the SLC 500 is provided by the following interfaces: 1747-SN Remote I/O Scanner The Remote I/O Scanner provides high-speed remote communication between an SLC processor and Allen-Bradley operator interface and control devices.
SLC 500 Programmable Controllers and I/O Modules 1747-ASB Remote I/O Adapter Module The Remote I/O Adapter module is a single-slot, RIO communication link module. It occupies the first slot (slot 0) of a 1746 remote chassis, where the SLC processor normally resides. The ASB module acts as a gateway between an SLC 500 remote I/O scanner and the I/O modules in the 1747-ASB remote and expansion chassis. The ASB module is compatible with all Allen-Bradley RIO scanners.
SLC 500 Programmable Controllers and I/O Modules Power Supplies Allen-Bradley offers seven different power supplies: three ac and four dc. 41 The ac supplies can be configured to operate using 120 or 240V ac. When configuring an SLC modular system, each chassis requires a power supply to provide power to the processor and I/O slots. Careful system configuration results in the best performance. Excessive loading of the power supply outputs can cause a power supply shutdown or premature failure.
SLC 500 Programmable Controllers and I/O Modules Selection Chart 42 Description 1746-P1 1746-P2 1746-P3 Line Voltage 85 to 132V ac 170 to 265V ac (47to 63 Hz) 85 to 132V ac 170 to 265V ac (47to 63 Hz) 19.2 to 28.8V dc Internal Current Capacity 2A at 5V dc 0.46A at 24V dc 5A at 5V dc 0.96A at 24V dc 3.6A at 5V dc 0.
SLC 500 Programmable Controllers and I/O Modules Chassis The chassis houses the processor and the I/O modules. There are four sizes of chassis that you can choose: 4-slot, 7-slot, 10-slot, and 13-slot. 43 Each chassis must have a power supply. The power supply mounts on the left side of the chassis. The first slot of the first chassis is reserved for the SLC processor or adapter module (1747-ASB, or 1747-ACN15 or -ACNR15). All components easily slide into the chassis along guides formed in the chassis.
SLC 500 Programmable Controllers and I/O Modules Programming Options The following sections describe programming options available for 44 the SLC 500. You can create and edit ladder programs using a personal computer or the 1747-PT1 Hand-Held Terminal (HHT, for SLC 5/01 and 5/02 processors only). RSLogix 500™ Programming Software The RSLogix 500 ladder logic programming package helps you maximize performance, save project development time, and improve productivity.
SLC 500 Programmable Controllers and I/O Modules Flexible, Easy-to-Use Editors Flexible program editors let you create application programs without worrying about getting the syntax correct as you create your program. A Project Verifier builds a list of errors that you can navigate to make corrections at your convenience. Powerful online editing features let you modify your application program while the process is still operating.
SLC 500 Programmable Controllers and I/O Modules Diagnostics and Troubleshooting Tools Quickly locate the specific area in the application that is causing a problem with Advanced Diagnostics. Diagnose the interaction of output instructions within a section of your program by viewing them at the same time. 46 Simultaneously examine the status of bits, timers, counters, inputs, and outputs all in one window with the Custom Data Monitor.
SLC 500 Programmable Controllers and I/O Modules 1747-PT1 Hand-Held Terminal and 1747-PTA1E Programming Memory Pak The Hand-Held Terminal (HHT) v2.03 is a powerful portable programming platform used to configure the SLC 500 Fixed, SLC 5/01, and the SLC 5/02 processors. It is used to enter or modify an application program, monitor the execution of the application program in real-time, or troubleshoot an application program. 47 The programming memory pak is interchangeable and available in four languages.
SLC 500 Programmable Controllers and I/O Modules SLC Programming Instruction Set 48 The following table shows the SLC 500 programming instruction set listed within their functional groups. Functional Group Description Relay-Type (Bit) The relay-type (bit) instructions monitor and control the status of bits. XIC, XIO, OTE, OTL, OTU, OSR Timer and Counter The timer and counter instructions control operations based on time or the number of events.
SLC 500 Programmable Controllers and I/O Modules 7 Steps to Successfully Configuring an SLC 500 System Step 1: Review the Family of Products and Determine Your Communication Requirements The SLC family has a wide variety of products offers some of the best communication options available for a small PLC. Take a couple of minutes to review the SLC product offerings. Step 2: Choose a CPU The SLC family offers five designs of CPUs, the SLC 5/01, 5/02, 5/03, 5/04, and 5/05.
SLC 500 Programmable Controllers and I/O Modules Power Supply Selection Example Select a power supply for chassis 1 and chassis 2 in the control system below. The example worksheet for this system is shown on page 52. A blank worksheet is shown on page 53. 50 ? ? 1747-PT1 ALL REMOVE ATTACH 7 XFER 4 +/- 1 ESC MODE 9 SEARCH 5 6 DUAL WORD MULTI POINT 2 3 RUNG 0 .PRE FAULT 8 FORCES SHIFT I .LEN 0 .ACC T .POS C : .
SLC 500 Programmable Controllers and I/O Modules Example Worksheet for Selecting 1746 Power Supplies for the Example System For a detailed list of device load currents, see page 54. Remember to consider future system expansion when selecting a power supply. Procedure 1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents.
SLC 500 Programmable Controllers and I/O Modules Blank Worksheet for Selecting 1746 Power Supplies If you have a multiple chassis system, make copies of the Worksheet for Selecting a Power Supply. For a detailed list of device load currents, see page 54. Remember to consider future system expansion when selecting a power supply. Procedure 52 1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents.
SLC 500 Programmable Controllers and I/O Modules Power Supply Loading Reference Table Use the table below to calculate the power supply loading and heat dissipation for each chassis in your SLC modular application. Definitions of some of the terms used in the table are provided on page 56. Hardware Component Catalog Numbers Maximum Current (A) at 5V dc at 24V dc Watts per Point Minimum Watts Total Watts Processors 1747-L511 0.350 0.105 NA 1.75 1.75 1747-L514 0.350 0.105 NA 1.75 1.
SLC 500 Programmable Controllers and I/O Modules Hardware Component Output Modules 54 Catalog Numbers Minimum Watts Total Watts 1746-OG16 0.180 — 0.033 0.900 1.50 0.135 — 0.775 0.675 6.90 1746-OV16 from page 53) Specialty Modules Watts per Point 1746-OV8 (continued Input and Output Modules Maximum Current (A) at 5V dc at 24V dc 0.270 — 0.388 1.400 7.60 (1) 1746-OV32 0.190 — 0.078 2.260 4.80 1746-OVP16 0.250 — 0.310 1.250 6.21 1746-OW4 0.045 0.045 0.133 1.310 1.
SLC 500 Programmable Controllers and I/O Modules Hardware Component Catalog Numbers Communication Modules 1747-ACN15 0.900 — NA 1747-ACNR15 0.900 — NA 1747-ASB 0.375 — NA 1747-BSN 0.800 0 1747-DCM 0.360 — NA 1.800 1.800 1747-KE 0.150 0.040(2) NA 3.750 3.800 1747-KFC15 0.640 0 NA 3.200 3.200 1747-SCNR 0.800 0.090 NA 1747-SDN 1.200 — NA 1747-SN 0.900 — NA 4.500 4.500 1747-AIC 0 0.085 NA 2.000 2.000 1747-DTAM 0 (3) NA 2.500 2.
SLC 500 Programmable Controllers and I/O Modules Dimensions 4-Slot Modular Chassis 11Dia. (0.433) 2 3 56 1.0 (0.04) 70 (2.76) 1 140 (5.51) 158 (6.22) 171 (6.73) 140 (5.51) 171 (6.73) 45 5.5 Dia. (0.217) 215 (1.77) 235 (8.46) (9.25) 261 (10.28) 145 (5.71) 14 (0.55) 7-Slot Modular Chassis 11Dia. (0.433) 2 3 5.5 Dia. (0.217) 175 (6.89) 1.0 (0.04) 1 171 (6.73) 140 171 (5.51) (6.73) 158 (6.22) 5.5 Dia. (0.217) 320 (12.60) 340 (13.39) 366 (14.41) 45 (1.77) 140 (5.51) 145 (5.71) 14 (0.
SLC 500 Programmable Controllers and I/O Modules 13-Slot Modular Chassis 11Dia. (0.433) 3 2 5.5 Dia. (0.217) 105 (4.13) 140 (5.51) 55 (2.17) 1 171 (6.73) 140 (5.51) 158 (6.22) 5.5 Dia. (0.217) 140 (5.51) 57 14 (0.55) 540 (21.26) 560 (22.05) 586 (23.07) 1.0 (0.04) 171 (6.73) 140 (5.51) 145 (5.71) 1. Dimensions for power supply catalog number 1746-P1 2. Dimensions for power supply catalog number 1746-P2, -P3, and -P5 3.
SLC 500, Data Highway Plus, MicroLogix 1000, RSLogix 500, PanelView and Dataliner are trademarks of Rockwell Automation. Ethernet is a registered trademark of Digital Equipment Corporation, Intel and Xerox Corporation. DeviceNet is a trademark of Open DeviceNet Vendor Association. Windows 95 is a registered trademark of Microsoft Corporation. Windows NT is a trademark of Microsoft Corporation.