Specifications
10
SLC 500™ Power Supplies
1746-IN004A-ML-P
SLC 500 Operation with 24V dc User Power Overcurrent Condition
5. Remove the protective label.
Catalog No. SLC Operation Recovery Procedure
1746-P1 Series A
(made in Japan)
P/S shutdown, CPU Fault Reload user program
1746-P1 Series A
(made in Malaysia-
current production)
24V dc user shutdown, CPU continues Correct overcurrent condition
1746-P2 Series A, B P/S shutdown, CPU Fault Reload user program
1746-P2 Series C 24V dc user shutdown, CPU continues Correct overcurrent condition
1746-P4 Series A P/S shutdown, CPU Fault Reload user program
1746-P5 Series A 24V dc user shutdown, CPU continues Correct overcurrent condition
1746-P6 Series A 24V dc user shutdown, CPU continues Correct overcurrent condition
!
ATTENTION:
For 1746-P1 (made in Malaysia), 1746-P2 Series
C, 1746-P5 Series A, and 1746-P6 Series A to aviod unexpected
operation due to 24V dc user power shutdown, monitor the 24V
dc user output with a 24V dc input channel.