MANUFACTURER DATA SHEET Power Supply Manufacturer: Allen-Bradley/Rockwell Model Number: 1746-P1 See www.geomartin.com for additional PDF datasheets Martin Part Number: VendorPartNumber: E-014624-01 AB # 1746-P1, Power Supply PDF File: Doc_000005_Cover.
This page is intentionally left blank
SLC 500™ Power Supplies (Catalog Numbers 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6, and 1746-P7) Installation Instructions Inside… page Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Genéralités . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Deutscher Abschnitt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SLC 500™ Power Supplies Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
English Section SLC 500™ Power Supplies (Catalog Numbers 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6, and 1746-P7) Overview Install your power supply using these installation instructions. The only tools you require are Flat head (1/8”) and Phillips head (1/4”, #2) screwdrivers. ! ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the power supplies.
4 SLC 500™ Power Supplies Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. WARNING: EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components or disconnect equipment unless power has been switched off or the area is known to be nonhazardous.
SLC 500™ Power Supplies 5 Install the Chassis Interconnect Cable (Optional) To connect up to three SLC 500™ chassis together, install the chassis interconnect cable before installing the power supply . SLC 500 chassis/A For more information, see the SLC 500 Modular Style Installation and Operation Manual (publication 1747-6.2). Power Supply Installation 1. Align the circuit board of the power supply with the card guides on the left side of the chassis . 2.
6 SLC 500™ Power Supplies Power Supply Wiring 1. Place the input voltage jumper to match the input voltage. (This does not apply to the 1746-P3, -P5, -P6, and -P7 power supplies, which do not have a jumper.) ! ATTENTION: Set the input jumper before applying power. Hazardous voltage is present on exposed pins when power is applied; contact with the pin may cause injury to personnel.
SLC 500™ Power Supplies 7 3. Connect incoming power. ATTENTION: Turn off incoming power before connecting wires; failure to do so could cause injury to personnel and/or equipment.
8 SLC 500™ Power Supplies 1746-P3 Wiring Considerations The information below describes special wiring considerations for the 1746-P3. ! ATTENTION: Any voltage applied to the 1746-P3 DC NEUT terminal will be present at the SLC logic ground and the processor DH-485 port.
SLC 500™ Power Supplies 1746-P3 Processor 9 SLC 500 Chassis Door Not Used DH±485 Port Not Used SLC Logic Resistor • Chassis • +24V dc DC Neut Chassis Ground Earth Ground 4. (Optional) For the 1746-P1, -P2,-P4, -P5 and -P6 power supplies, use PWR OUT +24V dc and PWR OUT COM terminals to power 24V dc sensors and loads. The terminals on the 1746-P1, 1746-P2, 1746-P5 and 1746-P6 provide an isolated, nonfused 200 mA, 24V dc power supply.
10 SLC 500™ Power Supplies SLC 500 Operation with 24V dc User Power Overcurrent Condition Catalog No.
SLC 500™ Power Supplies 11 Power Supply Undervoltage Operation SLC 500 controllers continue to operate (hold-up) for a short period of time if the input voltage to the power supply drops below the recommended operating voltage range. The controller continues to scan the user program and control I/O during this time. CPU hold-up for each power supply is shown on pages 9 and 10.
12 SLC 500™ Power Supplies General Specifications (Power Supplies P1, P2, P3, and P4) See page 10 for general specifications on the P5, P6, and P7 power supplies. Specification: 1746Description: P1 Line Voltage P2 85-132/170-265V ac 47-63 Hz Typical Line Power 135 VA Reqmnt. 180 VA P3 P4 19.2-28.8V dc 85-132/170-265V ac 47-63 Hz 90 VA 240 VA Maximum Inrush Current 20A Internal Current Capacity 2A at 5V dc 0.46A at 24V dc 5A at 5V dc 0.96A at 24V dc 3.6A at 5V dc 0.87A at 24V dc 10.
SLC 500™ Power Supplies 13 General Specifications (continued) Specification: 1746Description: P5 Line Voltage Typical Line Power Requirement Maximum Inrush Current P6 P7 90-146V dc 30-60V dc 10-30V dc1 85 VA 100 VA 12V dc input: 50 VA 24V dc input: 75 VA 20A 20A (required for turn-on) Internal Current Capacity 5A at 5V dc 0.96A at 24V dc 12V dc input: 24V dc input: 2.0A at 5V dc 3.6A at 5V dc 0.87A at 24V dc 0.46A at 24V dc See P7 current capacity chart on page 11.
14 SLC 500™ Power Supplies 24V dc Output Current 5V dc Output Current .87A 3.6A 0.625A 2.64A 0.46A 2.0A Input Voltage 10V dc 12.2V dc 19.2Vdc 15Vdc Physical Dimensions Controller: 1746P1 P2 P3 P4 Length: mm (in.) Depth: mm (in.) 65 (2.56) 85 (3.35) 140 (5.70) 110 (4.33) 145 (5.70) 85 (3.35) 140 (5.70) P5 P6 P7 1746-IN004A-ML-P Height: mm (in.) 140 (5.