System information
FCD 901 48
Issue R2A, 07.2009
XMP1 Release 5.5 System Description
RPS-XMP1 Remote Power supply module
Aastra Proprietary Information Page 9-33
9.13.2 RPS-XMP1 Remote Power supply module
9.13.2.1 Output voltages
Output FSP 1, FSP 2, FSP 3 and FSP 4
Nominal voltage [V] -116
Tolerance range [%]
3
Nominal load [A] 0.09
Pin tied to ground +
9.13.2.2 Remote supply ranges
Wires used
No. of
Repeater
Coverage
range with
0.9 mm
Coverage
range with
1.2 mm
Coverage
range with
1.4 mm
1 DA 1 19.2 km 36 km 49 km
1 DA 2 2 * 6,6km 2 * 12 km 2 * 16 km
1 DA 3 3 * 2.9 km 3 * 5.3 km 3 * 7.2 km
9.13.2.3 Supply voltage
Nominal voltage -48V / -60V DC voltage
Tolerance range -36V DC to -75V DC
Nominal input current
-48 V DC: 1.1 A
-60 V DC: 0.9 A
Upstream fuse
External automatic circuit breaker up to 4 A T
(time-lag) in each ungrounded pole of the power
supply.
9.13.2.4 Mechanical dimensions and weight
Length x width in mm 256 x 170
Weight 426 g
Operating altitude max. 3000 m
9.13.2.5 Interface classification acc. to EN 60950-1
UB -48/60 V TNV-2
+FSPx, -FSPx TNV-3
Signal output SIG SELV
9.13.2.6 EMC
In conjunction with the XMP1 system, the
RPS XMP1 remote power supply module
complies with the relevant EMC guidelines
(interference emission and immunity to
interference)
DIN EN 55022 – Limiting Value Class B
DIN EN 55024
ETSI EN 300 132-2
DIN EN 50 121-1
DIN EN 50 121-4
ETSI EN 300 386
DIN EN 60 870-2-1