System information

FCD 901 48
Issue R2A, 07.2009
XMP1 Release 5.5 System Description
XMP1 Subrack Grounding
Aastra Proprietary Information Page 8-23
8.7 XMP1 Subrack Grounding
Safety instructions
The rack or cabinet in which the XMP1 subrack is mounted must be
connected to the functional and protective earth (FPE) using a 16 mm
2
copper cable.
8.7.1 Installation in a rack or cabinet with unlacquered uprights
8.7.2 Installation in a rack or cabinet with lacquered uprights
CAUTION
Grounding must comply with the relevant national regulations!
In case of grounded racks or cabinets with unlacquered uprights, use
cage nuts for securing the XMP1 subrack.
If the XMP1 subrack is mounted in a grounded rack or cabinet with
lacquered uprights, secure it by means of cage nuts with grounding
claws.
In case of other mounting variants ground the XMP1 subrack by
means of a separate grounding cable.
Fuse and
connecting panel
48/60 V
FPE, 16 mm
2
XMP1 Subrack
Cage nuts
Cage nuts
Fuse and
connecting panel
48/60 V
FPE, 16 mm
2
XMP1 Subrack
Cage nuts with
grounding claw
Cage nuts with
grounding claw