User guide

5
Unit Data
*Note: 1/2 HP motors are direct drive. All other motors are belt drive with adjustable motor sheave.
** 2 HP motor not available in 265/1/60.
V2 General Data
Cabinet Size
A B C C+ D
Coil Face Area Designation
1 1 1 2 3 4 1 2
CFM Range
800 - 1200 800 - 2000 1800 - 3000 1800 - 4000 2000 - 4800 2500 - 6000 3000 – 6000 4300 - 10000
Electric Heating KW 7, 14 7, 14, 21 14, 21, 28, 35, 42 14, 28, 42, 56, 70
Blower
Quantity / Wheel Dia. / Type
1 / 10” / FC 1 / 15” / BI 1 / 18.5” / BI 1 / 18.5” / BI 1 / 27” / BI
Standard 1/2* 1 1 2 3
Oversize 2** 2 3 5
Double Oversize 3 5 7.5
Blower Motor
Maximum HP
Triple Oversize 5 7.5 10
FPT Drain Connection Size
3/4”
Pleated Filter Size
(Quantity)
16”x20”x2
(1)
24”x24”x2”
(1)
16”x 20”x2”
(4)
16”x20”x2”
(6)
16”x20”x2”
(9)
Table 5.2
H2 General Data
Cabinet Size
A B C C+ D
Coil Face Area Designation
1 1 1 2 3 4 1 2
CFM Range
800 - 1200 800 - 2000 1800 - 3000 1800 - 4000 2000 - 4800 2500 - 6000 3000 - 6000 4300 - 10000
Electric Heating KW 7, 14 7, 14, 21 14, 21, 28, 35, 42 14, 28, 42, 56, 70
Blower
Quantity / Wheel Dia. / Type
1 / 10” / FC 1 / 15” / BI 1 / 18.5” / BI 1 / 18.5” / BI 1 / 27” / BI
Standard 1/2* 1 1 2 3
Oversize 2** 2 3 5
Double Oversize 3 5 7.5
Blower Motor
Maximum HP
Triple Oversize 5 7.5 10
FPT Drain Connection Size
3/4”
Pleated Filter Size
(Quantity)
16”x20”x2
(1)
16”x20”x2
(2)
24”x24”x2”
(2)
24”x24”x2”
(3)
16”x20”x2”
(10)
Table 5.1
*Note: 1/2 HP motors are direct drive. All other motors are belt drive with adjustable motor sheave.
** 2 HP motor not available in 265/1/60.