H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Installation, Operation & Maintenance WARNING If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician.
Table of Contents Safety .............................................................................................................................................. 6 H3/V3 Base Model Description .................................................................................................... 10 General Information ...................................................................................................................... 16 Codes and Ordinances ..............................................
Index of Tables and Figures Tables: Table 1 - H3 and V3 Series Clearances ........................................................................................ 19 Table 2 - Control Wiring............................................................................................................... 24 Table 3 - Drain Trap Dimensions ................................................................................................. 26 Table 4 - Acceptable Air-Cooled Refrigeration Circuit Values .............
Figures: Figure 1 - Lockable Handle .......................................................................................................... 17 Figure 2 – Minimum Clearance Required for Access to Unit (V3 Series plan view) .................. 19 Figure 3 – Minimum Clearance Required for Access to Unit (H3 Series plan view) .................. 19 Figure 4 – H3 Series Platform Suspension Installation ................................................................
Safety Attention should be paid to the following statements: NOTE - Notes are intended to clarify the unit installation, operation and maintenance. CAUTION - Caution statements are given to prevent actions that may result in equipment damage, property damage, or personal injury. WARNING - Warning statements are given to prevent actions that could result in equipment damage, property damage, personal injury or death.
WARNING During installation, testing, servicing and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks. Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
CAUTION Rotation must be checked on all MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation.
WARNING Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturer’s usage instructions. Failure to follow instructions may result in equipment damage, injury or death. CAUTION Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latch are shipped with nut and bolts requiring tooled access.
H3/V3 Series Feature String Nomenclature : H3 - A R B - 3 - 0 - 1 6 1 C - 1 2 F : AA B B 14B 14A 13 12 11 10 9 8 7 6C 6B 6A 5C 5B 5A 4 3 2 1D 1C 1B Unit Feature Options 1A B3 B2 B1 A4 A3 A2 A1 CORR VLT MJREV ORENT SIZE GEN Model Options - 0 C 0 - F T B - 0 G 0 - 0 0 AAAC 0 0 B H3/V3 Base Model Description BASE MODEL Model Option A: COOLING SERIES AND GENERATION H3 = Horizontal - Back Intake, Front Discharge V3 = Vertical - Back Intake, Top Discharge A1: COOLING
H3/V3 Series Feature String Nomenclature : H3 - A R B - 3 - 0 - 1 6 1 C - 1 2 F :AABB 14B 14A 13 12 11 10 9 8 7 6C 6B 6A 5C 5B 5A 4 3 2 1D 1C 1B Unit Feature Options 1A B3 B2 B1 A4 A3 A2 A1 CORR VLT MJREV ORENT SIZE - 0 C 0 - F T B - 0 G 0 - 0 0 AAAC 0 0 B Model Option B: HEATING Feature 1: SUPPLY FAN B1: HEATING TYPE 0 = No Heating 1 = Hot Water 3 = Electric Heating 4 = Steam Distributing 1A: SUPPLY AIR BLOWER CONFIGURATION 0 = 1 Blower + Premium Eff.
H3/V3 Series Feature String Nomenclature : H3 - A R B - 3 - 0 - 1 6 1 C - 1 2 F : AABB - 0C0 - FTB 14B 14A 13 12 11 10 9 8 7 6C 6B 6A 5C 5B 5A 4 3 2 1D 1C 1B Unit Feature Options 1A B3 B2 B1 A4 A3 A2 A1 CORR VLT MJREV ORENT SIZE - 0 G 0 - 0 0 AAAC 0 0 B Feature 2: REFRIGERATION OPTIONS Feature 4: ADDITIONAL CONTROLS 0 = Standard - None A = Single Circuit External Hot Gas Bypass B = Dual Circuit External Hot Gas Bypass C = Heat Pump D = Option B + H E = Options B +
H3/V3 Series Feature String Nomenclature : H3 - A R B - 3 - 0 - 1 6 1 C - 1 2 F : AABB - 0C0 - FTB - 0 G 0 - 0 0 AAAC0 14B 14A 13 12 11 10 9 8 7 6C 6B 6A 5C 5B 5A 4 3 2 1D 1C 1B Unit Feature Options 1A B3 B2 B1 A4 A3 A2 A1 CORR VLT MJREV ORENT SIZE 0B Feature 6: FILTER BOX Feature 7: FILTER OPTIONS 6A: PRE FILTER BOX 0 = Standard - None A = 2” Pleated - 30% Eff. - MERV 8 B = 4” Pleated - 30% Eff. - MERV 8 C = 4” Pleated - 65% Eff.
H3/V3 Series Feature String Nomenclature : Feature 12: TONNAGE 0 = Standard - None A = 2 ton Capacity B = 3 ton Capacity C = 4 ton Capacity D = 5 ton Capacity E = 6 ton Capacity F = 7 ton Capacity G = 8 ton Capacity H = 10 ton Capacity J = 14 ton Capacity K = 17 ton Capacity L = 22 ton Capacity M = 25 ton Capacity N = 30 ton Capacity P = 31 ton Capacity Q = 34 ton Capacity R = 40-45 ton Capacity S = 50-55 ton Capacity T = 63 ton Capacity Feature 13: ADDED OR MODIFIED SYSTEMS 0 = Standard - None Feature 1
H3/V3 Series Feature String Nomenclature : 14B 14A 13 12 11 10 9 8 7 6C 6B 6A 5C 5B 5A 4 3 2 Feature 21: PULLEY COMBINATION Feature 23: TYPE 0 = Standard – None A = 1000-1400 rpm B = 1401-1800 rpm C = 1801-2200 rpm 0 = Standard X = Special Pricing Authorization Feature 22: WARRANTY 0 = Standard - 1 Year Parts 15 23 22 20 19 18 0 0 0 17 A0 0 0 0 0 21 - 0 C 0 - F T B - 0 G 0 - 0 0 AAAC 0 0 B 16 1D 1C 1B : AABB 15 H3 - A R B - 3 - 0 - 1 6 1 C - 1 2 F Unit Feature Option
General Information AAON® H3 and V3 Series indoor air handling units have been designed for indoor installation only. Units are assembled, wired, charged with dry nitrogen and run-tested at the factory. H3 and V3 Series units are not intended for residential use. Startup and service must be performed by a Factory Trained Service Technician. Certification of Cooling Models a. Certified as a commercial central air conditioner with or without electrically operated compressors. b.
WARNING Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty. Receiving Unit When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted on the carrier’s Freight Bill. A request for inspection by carrier’s agent should be made in writing at once.
CAUTION CRANKCASE HEATER OPERATION Some units are equipped with compressor crankcase heaters, which should be energized at least 24 hours prior to cooling operation, to clear any liquid refrigerant from the compressors. If power to the unit must be off for more than an hour, turn the thermostat system switch to "OFF", or turn the unit off at the control panel, and leave the unit off until the main power switch has been turned on again for at least 24 hours for units with compressor crankcase heaters.
Locating the Unit Placement of the unit relative to ductwork, electrical and plumbing must be carefully considered. Return air plenum or duct can be mounted directly to the return air flanges. Use flexible gasket material to seal the duct to the unit. Verify floor, foundation or suspension support can support the total unit weight, including accessory weights. Unit must be level in both horizontal axes to support the unit and reduce noise and vibration from the unit.
Suspended Units H3 Series horizontal air handling units are equipped for suspended installations. The unit should be lifted into position by supporting the unit with the skid used for shipping. The air handling unit must be installed level and care should be taken to prevent damage to the cabinet. Other installation provisions may be necessary according to job specifications. Figure 4 and Figure 5 show factory recommended methods for suspended installations.
H3 Series Top View Left Hand Side Return Air “Back” Supply Air “Front” Air Flow Right Hand Side Connections and service access on right side for right hand orientation Consider the air flow to be hitting the back of your head. Figure 6 - H3 Series Unit Orientation V3 Series Top View “Front” Right Hand Side Left Hand Side Supply Air Connections and service access on right side for right hand orientation Return Air “Back” Consider the air flow to be hitting the back of your head.
Lifting and Handling the Unit Before lifting unit, be sure that all shipping material has been removed from unit. Care should be taken if using spreader bars, blocking or other lifting devices to prevent damage to the cabinet, coil or fans. WARNING UNIT HANDLING Incorrect lifting can cause damage to the unit, injury or death. Lifting equipment capacity should exceed unit weight by an adequate safety factor. Always test lift unit not more than 24 inches high to verify proper center of gravity lift point.
inches away from all components and wiring to prevent damage due to drilling or cutting. 2. Drill a pilot hole all the way through the foam panel. 3. Using a hole saw cut the hole through the metal on both sides of the foam part. 4. With a knife cut the foam out of the hole. 5. After the conduit is installed in the hole caulk the entire perimeter of the hole on both sides with an industrial grade silicone sealant or a duct seal compound.
terminal. Contact your local power company for line voltage corrections. Installing contractor must check for proper motor rotation and check blower motor amperage listed on the motor nameplate is not exceeded. CAUTION Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Supply fan motors should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
Duct Connection Attach duct to flanges provided on the unit. The installer is responsible for sealing ducts to the flanges to prevent water leaks. Condensate drain trapping and piping should conform to all applicable governing codes. Note: The drain pan connection(s) is a 1” MPT fitting. Refer to Figure 6 and Figure 7 for duct connection locations. Ductwork should be sized in accordance with the ASHRAE Handbook. Ductwork should be installed in accordance with NFPA Standard 90A.
Table 3 - Drain Trap Dimensions Draw-Through Drain Pan Pressure Trap Dimensions Negative Static X X/2 (inches of water) (inch) (inch) -0.50 1.50 0.75 -1.00 2.00 1.00 -1.50 2.50 1.25 -2.00 3.00 1.50 -2.50 3.50 1.75 -3.00 4.00 2.00 -3.50 4.50 2.25 -4.00 5.00 2.50 Heating Coils One or two row hot water and steam heating and preheating coils can be factory installed. All valve controls for heating coil operation are field supplied and field installed.
CAUTION This section is for information only and is not intended to provide all details required by the designer or installer of the refrigerant piping between the condenser or condensing unit and the air handling unit. AAON is not responsible for interconnecting refrigerant piping. Consult ASHRAE Handbook – Refrigeration and ASME Standards. Only clean ACR tubing should be used. Piping should conform to generally accepted practices and codes. exposing the coils to moisture.
Modulating Hot Gas Reheat Piping: 1. Run a hot gas reheat line from the condensing unit and connect it to the inlet of the stub-out on the reheat coil. The inlet connection is the top (or highest) stub-out of the reheat coil. Connect the hot gas line from the outdoor unit to the upper stub-out connection of the reheat coil. 2. Run a liquid line from the discharge of the reheat coil through a tee connection. Run a liquid line from the condenser, through a check valve to the other side of the tee.
Liquid refrigerant traveling upwards in a riser loses head pressure. If the evaporator is below the condenser, and the liquid line does not include risers, the gravitational force will increase the pressure of the liquid refrigerant. This will allow the refrigerant to withstand greater frictional losses without the occurrence of flashing prior to the TXV. A moisture-indicating sight glass may be field installed in the liquid line to indicate the occurrence of premature flashing or moisture in the line.
collects in the compressor from causing damage or wear. Make sure to provide support to maintain suction line positioning, and insulate completely between the evaporator and condensing unit. It is important to consider part load operation when sizing suction lines. At minimum capacity, refrigerant velocity may not be adequate to return oil up the vertical riser. Decreasing the diameter of the vertical riser will increase the velocity, but also the frictional loss.
from the compressor discharge to the low pressure side of the system in order to keep the evaporator from freezing and to maintain adequate refrigerant velocity for oil return at minimum load. Hot discharge gas is redirected to the evaporator inlet via an auxiliary side connector (ASC) to false load the evaporator when reduced suction pressure is sensed. Field piping between the condensing unit and the evaporator is required.
Hot Gas Reheat Guidelines Maintain velocities below a maximum of 3,500 fpm. A general minimum velocity guideline is 2,000 fpm. Startup (See back of the manual for startup form) WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit. Electric shock hazard.
If the band is field installed, a hand held pop-rivet tool is recommended for connecting the band ends together. Caution must be taken to assure that the band is tightly installed and no damage, denting or alteration to the wheel or blades occurs during the installation.
Filters Do not operate the unit without filters in place. Unit should be checked for correct filter placement during startup. Operation of the equipment without filters will result in a clogged evaporator coil. CAUTION Before completing startup and leaving the unit a complete operating cycle should be observed to verify that all components are functioning properly.
Subtract the saturated temperature from the measured suction line temperature to determine the evaporator superheat. Compare calculated superheat to the table below for the appropriate unit type and options. CAUTION DO NOT OVERCHARGE! Refrigerant overcharging leads to excess refrigerant in the condenser coils resulting in elevated compressor discharge pressure.
4. The sensing bulb is fully insulated. 5. If the sensing bulb is installed on a vertical portion of the suction line, the sensing bulb should be placed upstream of suction line trap. Table 6 - R-410A Refrigerant Temperature-Pressure Chart °F 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 36 PSIG 78.3 80.0 81.8 83.6 85.4 87.2 89.1 91.0 92.9 94.9 96.8 98.8 100.9 102.9 105.0 107.1 109.2 111.4 113.6 115.8 118.1 120.3 122.7 125.0 127.4 129.8 132.
Operation Maintenance Unit operations should be controlled with thermostat or unit controller, never at the main power supply, except for emergency or complete shutdown of the unit. (See back of the manual for maintenance log.) Electric Heating Operation When a call for heating (G and W1, W2, etc.) is made the supply fan motors and electric resistance heaters will energize.
E-Coated Coil Cleaning Documented routine cleaning of e-coated coils is required to maintain coating warranty coverage. WARNING Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts. Surface loaded fibers or dirt should be removed prior to water rinse to prevent restriction of airflow. If unable to back wash the side of the coil opposite of the coils entering air side, then surface loaded fibers or dirt should be removed with a vacuum cleaner.
dust, soot, greasy residue, lint and other particulate: Enviro-Coil Concentrate, Part Number HEC01. Recommended Chloride Remover CHLOR*RID DTS™ should be used to remove soluble salts from the e-coated coil, but the directions must be followed closely. This product is not intended for use as a degreaser. Any grease or oil film should first be removed with the approved cleaning agent. Remove Barrier - Soluble salts adhere themselves to the substrate.
WARNING Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts. It is strongly recommended that filter media be replaced monthly. Filters are located upstream of the evaporator coil. Open access panel and pull filters straight out to inspect all of the filters. Replace filters with the size indicated on each filter. Arrow on the replacement filters must point towards the blower.
Filter Information Feature 6A 0 A B C D E F G H J Feature 6A 0 A B C D E F G H J Table 7 - H3 Series A Cabinet Pre Filters (Quantity) Size Type No Pre Filters (1) 16” x 25” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (1) 16” x 25” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (1) 16” x 25” x 2” and (1) 16” x 25” x 4” Pleated, 30% Eff, MERV 8 and Pleat
Feature 6A 0 A B C D E F G H J Feature 6A 0 A B C D E F G H J 42 Table 9 - H3 Series B Cabinet Pre Filters (Quantity) Size Type No Pre Filters (2) 16” x 20” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (2) 16” x 20” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (2) 16” x 20” x 2” and (2) 16” x 20” x 4” Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, ME
Feature 6A 0 A B C D E F G H J Feature 6A 0 A B C D E F G H J Table 11 - H3 Series C Cabinet Pre Filters (Quantity) Size Type No Pre Filters (2) 20” x 20” x 2" and Pleated, 30% Eff, MERV 8 (1) 16” x 20” x 2" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (2) 20” x 20” x 4" and (1) 16” x 20” x 4" Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 (2) 20” x 20” x 2" and Pleated, 30% Eff, MERV 8 and (1) 16” x 20” x 2" Pleated, 65% Eff, MERV 11 and Pl
Feature 6A 0 A B C D E F G H J Feature 6A 0 A B C D E F G H J 44 Table 13 - H3 Series D Cabinet Pre Filters (Quantity) Size Type No Pre Filters (1) 20” x 20” x 2” and Pleated, 30% Eff, MERV 8 (4) 16” x 20” x 2" Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (1) 20” x 20” x 4” and (4) 16” x 20” x 4" Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 (1) 20” x 20” x 2” and Pleated, 30% Eff, MERV 8 and (4) 16” x 20” x 2" Pleated, 65% Eff, MERV 11 an
Feature 6A 0 A B C D E F G H J Feature 6A 0 A B C D E F G H J Table 15 - H3 Series E Cabinet Pre Filters (Quantity) Size Type No Pre Filters (10) 16” x 20” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (10) 16” x 20” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (10) 16” x 20” x 2” and (10) 16” x 20” x 4” Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, M
Feature 6B 0 A B C D E F G H J Feature 6B 0 A B C D E F G H J 46 Table 17 - H3 Series A Cabinet Unit Filters (Quantity) Size Type No Unit Filters (1) 16” x 25” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (1) 16” x 25” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (1) 16” x 25” x 2” and (1) 16” x 25” x 4” Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff,
Feature 6B 0 A B C D E F G H J Feature 6B 0 A B C D E F G H J Table 19 - H3 Series B Cabinet Unit Filters (Quantity) Size Type No Unit Filters (2) 16” x 20” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (2) 16” x 20” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (2) 16” x 20” x 2” and (2) 16” x 20” x 4” Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MER
Feature 6B 0 A B C D E F G H J Feature 6B 0 A B C D E F G H J 48 Table 21 - V3 Series C Cabinet Unit Filters (Quantity) Size Type No Unit Filters (4) 16” x 20” x 2” Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 Pleated, 65% Eff, MERV 11 (4) 16” x 20” x 4” Pleated, 85% Eff, MERV 13 Pleated, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8 Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11 (4) 16” x 20” x 2” and (4) 16” x 20” x 4” Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff,
Feature 6C 0 A B C D E F G Feature 6C 0 A Feature 6C 0 A B C D E F G Feature 6C 0 A Table 23 - H3 Series A Cabinet Final Filters (Quantity) Size Type No Final Filters (1) 16” x 25” x 2” Pleated, 30% Eff, MERV 8 Cartridge, 65% Eff, MERV 11 (1) 16” x 25” x 12” Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Cartridge, 65% Eff, MERV 11 (1) 16” x 25” x 2” and Pleated, 30% Eff, MERV 8 and (1) 16” x 25” x 12” Cartridge, 85% Eff, MERV 13 Pleated, 30% Eff, MERV 8 and Cartrid
Feature 6C 0 A B C D E F G Feature 6C 0 A Feature 6C 0 A B C D E F G Feature 6C 0 A 50 Table 27 - H3 Series C Cabinet Final Filters (Quantity) Size Type No Final Filters (2) 20” x 20” x 2” and Pleated, 30% Eff, MERV 8 (1) 16” x 20” x 2" Cartridge, 65% Eff, MERV 11 (2) 20” x 20” x12” and Cartridge, 85% Eff, MERV 13 (1) 16” x 20” x 12" Cartridge, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and (2) 20” x 20” x 2” and Cartridge, 65% Eff, MERV 11 (1) 16” x 20” x 2" Pleated, 30% Eff, MERV 8 and and Cartridge,
Feature 6C 0 A B C D E F G Feature 6C 0 A Table 31 - H3 Series E Cabinet Final Filters (Quantity) Size Type No Final Filters (10) 16” x 20” x 2” Pleated, 30% Eff, MERV 8 Cartridge, 65% Eff, MERV 11 (10) 16” x 20” x 12” Cartridge, 85% Eff, MERV 13 Cartridge, 95% Eff, MERV 14 Pleated, 30% Eff, MERV 8 and Cartridge, 65% Eff, MERV 11 (10) 16” x 20” x 2” and Pleated, 30% Eff, MERV 8 and (10) 16” x 20” x 12” Cartridge, 85% Eff, MERV 13 Pleated, 30% Eff, MERV 8 and Cartridge, 95% Eff, MERV 14 Table 32 - V3 Serie
Refrigerant Piping Diagrams Figure 11 – A/C only piping, AHU above CU 52
Figure 12 – A/C only piping, AHU below CU 53
Figure 13 – Modulating hot gas reheat piping, AHU above CU 54
Figure 14 – Modulating hot gas reheat piping, AHU below CU 55
Figure 15 – Hot gas bypass piping, AHU above CU 56
Figure 16 – Hot gas bypass piping, AHU below CU 57
Figure 17 – Modulating hot gas reheat with hot gas bypass piping, AHU above CU 58
Figure 18 – Modulating hot gas reheat with hot gas bypass piping, AHU below CU 59
Figure 19 – Heat pump piping, AHU above CU 60
Figure 20 – Heat pump piping, AHU below CU 61
Figure 21 – Heat pump with modulating hot gas reheat piping, AHU above CU 62
Figure 22 – Heat pump with modulating hot gas reheat piping, AHU below CU 63
H3/V3 Series Startup Form Job Name:_______________________________________________ Date:______________ Address:______________________________________________________________________ ______________________________________________________________________________ Model Number:_________________________________________________________________ Serial Number:_____________________________________________ Tag:_______________ Startup Contractor:______________________________________________________________ Address:
Ambient Temperature Ambient Dry Bulb Temperature ________°F Ambient Wet Bulb Temperature ________°F Supply Fan Assembly Alignment Number Check Rotation hp L1 Nameplate Amps________ L2 L3 1 2 Band Size_____________________ VAV Controls_________________ VFD Frequency________________ Compressors/DX Cooling Check Rotation Number L1 L2 L3 Head Pressure PSIG Suction Pressure PSIG Crankcase Heater Amps 1 2 3 4 Refrigeration System 1 - Cooling Mode Saturated Pressure Temperature Discharge Suction L
Refrigeration System 4 - Cooling Mode Saturated Pressure Temperature Discharge Suction Liquid Line Temperature Refrigeration System 1 - Heating Mode (Heat Pump Only) Saturated Line Pressure Temperature Temperature Discharge Suction Liquid Refrigeration System 2 - Heating Mode (Heat Pump Only) Saturated Line Pressure Temperature Temperature Discharge Suction Liquid Refrigeration System 3 - Heating Mode (Heat Pump Only) Saturated Line Pressure Temperature Temperature Discharge Suction Liquid Refrigeration S
Unit Configuration Water-Cooled Condenser Air-Cooled Condenser No Water Leaks Condenser Safety Check Water Flow ________ gpm Water Inlet Temperature ________°F Water Outlet Temperature ________°F Mixing Box Dampers Operation Check Damper Wiring Check Gears Check Damper Actuator Type:__________________________________________________________ Economizer Changeover Type and Operations:_______________________________________ Water/Glycol System 1.
Air-Cooled Condenser Fans Alignment Number Check Rotation hp L1 Nameplate Amps________ L2 L3 1 2 3 4 5 6 Electric Heating Stages__________ Stage 1 2 3 4 Limit Lockout Amps Aux. Limit Lockout Stage 5 6 7 8 Amps Electric Preheating Limit Lockout Aux.
Maintenance Log This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper startup, maintenance and servicing of the equipment falls to the owner and qualified licensed technician. Entry Date Action Taken Name/Tel.
Literature Change History June 2010 Revision of the IOM adding PVC and CPVC piping Caution. June 2011 Update of the IOM adding the electronic startup form.
AAON 203 Gum Springs Rd. Longview, TX 75602-1721 Phone: 903-236-4403 Fax: 903-236-4463 www.aaon.com H3/V3 Series Installation, Operation & Maintenance R94201 · Rev. A · 140521 (ACP J00188) It is the intent of AAON to provide accurate and current product information. However, in the interest of product improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice, obligation, or liability. Copyright © AAON, all rights reserved throughout the world.