Technical Data Sheet No.
Aalborg7 is a registered trademark of Aalborg Instruments & Controls. NOTE: Aalborg reserves the right to change designs and dimensions at its sole discretion at any time without notice. For certified dimensions please contact Aalborg7.
TABLE OF CONTENTS (a) a.1 a.2 a.3 UNPACKING THE SDPROC COMMAND MODULE.......................................1 Inspect Package for External Damage........................................................ 1 Unpack the Command Module................................................................... 1 Returning Merchandise for Repair...............................................................1 (b) b.1 b.2 b.2.1 b.2.2 b.2.3 b.2.4 b.2.5 INSTALLATION...........................................................
e.2.9 e.2.9.1 e.2.9.2 e.2.10 e.3 e.3.1 e.3.2 e.3.3 e.3.4 e.3.5 e.3.6 e.3.7 e.3.7.1 e.3.7.2 e.3.7.3 e.3.7.4 e.3.7.5 e.3.8 e.3.8.1 e.3.8.2 e.3.8.3 e.3.8.4 e.3.8.5 e.3.9 e.3.9.1 e.3.9.2 e.3.9.3 e.3.9.4 e.3.10 e.3.10.1 e.3.10.2 e.3.10.3 e.3.11 e.3.12 e.3.13 Program Settings Display............................................................................14 Batch Program Settings Display.................................................................14 Timer Program Settings Display..........................
(i) i.1 i.2 i.2.1 i.2.2 i.2.3 i.3 i.4 i.5 NETWORK COMMUNICATION INTERFACE (OPTIONAL).............................. 42 0Base-T RJ-45 Pinout................................................................................42 Network Protocols......................................................................................42 DHCP..........................................................................................................42 DNS....................................................................
(a) UNPACKING THE SDPROC COMMAND MODULE a.1 Inspect Package for External Damage Your SDPROC Command Module was carefully packed in a sturdy cardboard carton, with anti static cushioning materials to withstand shipping shock. Upon receipt, inspect the package for possible external damage. In case of external damage to the package contact the shipping company immediately. a.2 Unpack the Command Module Open the carton carefully from the top and inspect for any sign of concealed shipping damage.
b.2 Electrical Connections b.2.1 Connecting Flow Transducers Attach the 15 pin “D” connector cable(s) between the interface panel on the rear of the SDPROC and the Flow Meter/Controller transducer(s). (Number of channels will vary from one to four in accordance with configuration and options purchased.) Figure b-1, Interface Panel for SDPROC. No connection with the DATA IN/OUT, RELAYS or RS 232 connector is required for operating the system.
Use of the SDPROC in a manner other than that specified in this manual or in writing from Aalborg7, may impair the protection provided by the equipment. Figure b-2, Pin out chart for CHANNEL l/2/3/4 “Flow Transducers” connector. b.2.2 Power Input Make sure the POWER switch on the back of the SDPROC is OFF. On one end of the AC line cord is a universal connector that will fit securely into the AC inlet receptacle at the rear of the SDPROC. Make this connection.
Turn the POWER OFF when not in use. At the rear of the SDPROC, there is a 25 pin Male Type “D” connector “RELAYS”. The pin outs are as follows: b.2.5 Relays Interface (c) DESCRIPTION Microprocessor driven digital Command Modules are used in conjunction with any analog or digital mass flow meters or controllers with 0-5 Vdc input /output signals. One, two, three and four channel Command Module configurations are available.
FUSE: 2A on input and output power line. When changing, unplug the device from power source. Replace only with fuse 5mm 2A/250V FF. DISPLAY: 24x2 LCD dot matrix with backlight; 24x2 Vacuum Florescent display optional. READINGS: 0 to 100% scale is standard; the following units of measure are supported: %F.S., SLPM, SLPH, SCCM, SCCH, SCFM, SCFH, SCMM, SCMH, LBPM, LBPH, GRPM, GRPH. ADC/DAC RESOLUTION: 12 bits (0.025%). DIGITAL COMMUNICATION STANDARD: RS-232.
(e) OPERATING INSTRUCTIONS There are four buttons on the front panel of the SDPROC from which all functions can be controlled or set. These are labeled “ESC”, “UP”, “DOWN”, and “ENTER”. Figure e-1, Control Panel for SDPROC. e.1 Preparation and Warm Up It is assumed that the SDPROC and the Mass Flow Meter(s) and/or Controller(s) have been correctly installed as described in this and the AFM/AFC/DFC/GFM/GFC manuals. Turn the POWER switch to the ON position.
The Main Display will indicate the following info: = “F” current flow rate in % F.S. (NOTE: An “I” is indicated on the display immediately following the displayed flow when the SDPROC is set for internal reference and “E” for external reference.) = “S” current set point in % F.S. = “V” valve status by displaying a “CLS” for CLOSE, “OPN” for OPEN or “AUT” for AUTO. = “A” alarm status by displaying a “D” for disabled, “N” for no alarm events, “L” for Low alarm and “H” for High alarm.
Set Point Display for 1 channel SDPROC The UP button under the “+” and DOWN button under the “-” will increase and decrease the set point respectively. Once set, press the ENTER button under EXIT on the display to return to the Main Display. This set point is only applicable when the SDPROC is used in INTERNAL REFERENCE mode. From the Set Point Screen in order to change the mode of operation press the Esc button under VALVE on the display. The following display will appear.
Setup Channel screen allows to configure: = General device settings: Int./Ext. Reference, Gas density, Engineering Units, Full Scale Flow in L/Min and Relays assignment. = Alarm Properties: Mode, High and Low settings in % F.S., Delay Time, Action. = Totalizer Properties: Mode, Start Flow, Stop Volume, Action. = Program Properties: Batch parameters and Timer Settings. Press the Esc button under GENER. on the display in order to make General settings.
e.2.6.3 Setup Engineering Units Display Press the UP or DN button, to change current engineering units. The following engineering units are supported: %F.S., SLPM, SLPH, SCCM, SCCH, SCFM, SCFH, SCMM, SCMH, LBPM, LBPH, GRPM, GRPH. If no more settings are required, press the ENTER button under EXIT on the display, to go back to the Main Display. Press the ENTER button under NEXT on the display in order to go to the Full Scale Flow Rate screen. The following Setup Full Scale Flow Rate Display will appear. e.
The following display will appear. Press ESC button under NEXT on the display or the ENTER button under EXIT on the display, to go back to the Main Display. e.2.7 Setup Alarm Display Before enabling the Alarm make sure all alarm settings are configured properly. High and Low alarm values have to be entered in %F.S. engineering units. ALARM conditions become valid when the difference between current readings and installed set points is equal or more than corresponding values of high and low alarm levels.
e.2.7.4 Setup Alarm Delay Display Alarm Delay specifies the time interval in seconds the Alarm conditions have to be True (without any interruption) before Alarm will be activated. If zero value is set, the Alarm will be activated immediately after Alarm conditions are met. Pressing (+) or (-) will increment or decrement Alarm Delay settings per 1 second respectively. If no settings required for Alarm Action press the ENTER button under EXIT on the display, to go back to the Main Display.
e.2.8.1 Setup Totalizer Mode Display To change Totalizer Mode in ENABLED or DISABLED, press the button (UP, DOWN respectively) directly below the mode shown on the display. To return to the Main Display, press the ENTER button under EXIT on the display. Press the ESC button under NEXT on the display to go to the Totalizer Start settings. The following Setup Totalizer Start Flow Display will appear. e.2.8.
To change Totalizer Action in NONE, BUZZER or VALVE, press the button (ESC, UP, DOWN respectively) directly below the text shown on the display. If Buzzer action is chosen, the audible signal will be activated when Totalizer conditions become true. In order to deactivate the audible signal during operation press any button on the key pad (NOTE: The Totalizer has to be reset to zero or disabled).
The same is true for 0 seconds, pressing the (-) button will rollover time settings to 99999 seconds. Press the ENTER button under MULT on the display, to change the value of the multiplier to 10. Continuing to press the ENTER button under MULT on the display, will change the value of the multiplier first to 100 and then back to 1. When complete with TIME settings for the first step of the Batch program, press the ESC button under NEXT on the display, to go to the SETPOINT screen.
e.2.9.2 Timer Program Settings Display The Timer Flow Control allows execution of a custom, user preset program of up to 96 steps. Each step can be pre-programmed for a particular date, time, and set point value in % F.S.. Every step has two fields: starting date, time and set point in % F.S. Before executing, the program should be entered in the program table in the format: TIME/DATE [XX.XX XX/XX/XXXX] - SETPOINT [% F.S.].
e.2.10 Status Check While in the Main Display press the UP button on the front panel of the SDPROC. The Relays Assignment Status will appear. Relays Status Display One channel SDPROC Pressing the UP button again will bring up the Totalizer Settings screen. Pressing the DOWN button will return to the Main Display. Totalizer Settings Display One channel SDPROC Press UP one more time to return to the Main Display. E.3 MULTI CHANNEL SDPROC e.3.
e.3.2 Main Display After a few seconds, the Start up display will clear, and the Main Display will appear. Main Display for 2 channel SDPROC Main Display for 3 channel SDPROC Main Display for 4 channel SDPROC Readings are linear 0 to 100% of full scale. Direct engineering units are available on another screen. A proportionally linear 0 to 5 VDC or 4 to 20 mA output signal may be monitored simultaneously at the 25 pin “D” connector at the back of the SDPROC (see section b.2.4).
nel 3 has been selected.) The following Set Point Display will appear. e.3.4 Set Point Display Set point Display Multi channel SDPROC The screen above assumes that the full scale flow rate for channel #3 is set to 5.0 SLPM and current units of measure is SLPM. The UP button under the “+” and DOWN button under the “-” will increase and decrease the set point respectively.
e.3.7 Setup Channel Display Pressing the Down button under Main Display screen (see section e.3.2) will display SETUP CHANNEL screen shown below. Setup Channel Display for Multi channel SDPROC Press the button on the SDPROC panel under the appropriate channel number displayed. This will select that channel for device settings configuration. (For this manual, channel 3 has been selected.) The following display will appear. Setup Channel screen allows to configure: = GENERAL DEVICE SETTINGS: Int./Ext.
e.3.7.2 Setup Gas Density Display The proper settings of the gas density (in grams per liter) are required for mass based engineering units (LBPH, LBPM, GrPH, GrPM). Press the ENTER button under (--->) on the display, to move the flashing cursor to the desired position. Pressing (+) or (-) will increment or decrement a particular digit respectively. The numbers will change from 0 to 9 and next to the decimal point (.).
change the decimal point to any desired digit, next move the cursor to the required position, and adjust it to the decimal point with the (+) or (-) button. When complete with Full Scale Flow Rate settings, press the ESC button under NEXT on the display, to go to the Relays Assignment screen. The following Setup Relays Assignment Display will appear. e.3.7.5 Setup Relays Assignment Display Two sets of dry contact relay are available for each channel.
NEXT on the display to go to the Alarm Low settings. The following Setup Alarm Low Display will appear. e.3.8.2 Setup Alarm Low Display Pressing (+) or (-) will increment or decrement Low Alarm settings per 0.1% F.S. respectively. If no settings are required for High Alarm press the ENTER button under EXIT on the display, to go back to the Main Display. Press the ESC button under NEXT on the display to go to the Alarm High settings. The following Setup Alarm Low Display will appear. e.3.8.
In order to deactivate the audible signal during operation, press any button on the key pad (NOTE: Alarm Conditions have to be removed or Alarm for the corresponding channel has to be disabled). If Valve action is chosen the power to the mass flow controller valve will be shut off, allowing the valve to mechanically close. If the Valve was shut off as the result of the Alarm action, in order to go back to normal operation the Valve mode has to be changed to AUTO (See section e.3.5).
under NEXT on the display to go to the Totalizer Stop settings. The following Setup Totalizer Stop Volume Display will appear. e.3.9.3 Setup Totalizer Stop Volume Display The proper setting of the Totalizer Stop Volume (in volume/mass based engineering units) is required if the Totalizer is set to Enabled. The engineering unit for Totalizer Stop Volume has to be related to the current active engineering unit.
There are three program options for multi channel SDPROC: BATCH, TIMER and RATIO flow control. e.3.10.1 Batch Program Settings Display Batch Flow Control allows execution of a custom, user preset program of up to sixteen steps. During execution of the program the user can activate or deactivate the LOOP mode. Various flow configurations may be pre-programmed: ramping, pulsing, linearized increasing and/or decreasing of the flow.
BATCH mode control screen with batch disabled The two digit number after “SE:” indicates the number of the enabled steps for executions. Press the UP button under STEPS on the display, to change the number of steps from the batch program to be executed. With 16 steps enabled on the screen, pressing the Up button one more time will rollover the number of steps back to 1. Press the ENTER button under LOOP on the display, to toggle the loop control ON and OFF.
the ENTER button to move the flashing cursor to the date position (month, date and year) respectively. Make sure date and time entered is not in the past (otherwise this step of the program will not be executed). When complete with TIME and DATE settings for first step of the Timer program, press the ESC button under NEXT on the display, to go to the SETPOINT screen. The following display will appear.
By default, Ratio Mode is disabled for each channel. In order to be able to enable Ratio Mode, the value of the ratio in % for a particular channel has to be more than 0%. It is recommended to begin Ratio settings from the master channel #1 (master channel has to be set to the highest value from the mixture). For example, if four gas mixtures are desired with ratios: Gas#1=30%, Gas#2= 25%, Gas#3=25% and Gas#4=20% the Gas#1 has to be set on channel#1 (master channel).
Make sure that the total value of the mixture is equal to 100% in the end of the ratio settings for all required channels. When complete with ratio value settings for all required channels, go to the ratio mode settings screen for each required channel and change the ratio mode from DISABLED to ENABLED. Make sure that the reference for set point is set to PROGRAM RATIO mode for all required channels in order for the Ratio program to be executed (see section e.3.7.1).
e.3.12 Real-time Clock Settings Real Time Clock Settings Display for SDPROC Normally date and time for the Real-time Clock are set by the factory, unless the battery was replaced, or the CPU core was removed from the main board of the SDPROC. In order to change date and time settings press the ENTER button under SET on the display. This will activate the flashing cursor on the hours position. Pressing (+) or (-) will increment or decrement the time settings (hours).
Pressing the UP button again will bring up the Alarm Mode Status for all channels. Alarm Mode Status Display for Multi channel SDPROC Pressing the UP button again will bring up the Totalizer Mode Status for all channels. Totalizer Mode Status Display for Multi channel SDPROC Press UP one more time to return to the Main Display. NOTE: Pressing the Down button from any of the status screens will switch status display to one step back. (f) MAINTENANCE The SDPROC does not require any regular maintenance.
Calibration Mode Display Proceed with instructions outlined in sections g.1 and g.2. g.1 Digital to Analog (D/A) Slope Calibration Select the D/A calibration mode from the Calibration Menu. The following display will appear. The digital to analog (D/A) slope has to be calibrated for each channel , NOTE: individually! Using an accurate digital multimeter, measure the A/D output DC voltage between pins 9 (positive) and 10 (ground) of the Channel 1 15 pin “D” connector.
The display should show the D/A value between 3900 and 4095. Save the D/A slope parameter by pressing the CAL (ENTER button).Proceed with D/A calibration for as many channels as required. When digital to analog (D/A) slope is calibrated for last available channel, the following display will appear. g.2 Analog to Digital (A/D) Calibration Select the A/D calibration mode from the Calibration Menu. The following display will appear. Connect exactly 5.
Press any key when done with 5.000 Vdc connections. The following display will appear. The display should show the A/D offset values between 3850 and 4095. If any value is outside of those limits, the PC board is defective. Save the A/D offset parameters by pressing the CAL (ENTER button). The following display will appear. Calibration of the SDPROC is complete. Press any key to return to the Calibration Mode Display, then press the EXIT button to return to the Main Display.
The protocol described below allows for communications with the unit using either a custom software program or a “dumb terminal.” All values are sent as printable ASCII characters. The command parameters are delimited by a space character and the command string is always terminated with a carriage return character, (line feeds are automatically stripped out by the SDPROC). The structure of the command string: Cmd Arg1 Arg2 Arg3 Arg4 [CR] Where: Cmd The two or three characters command from the table below.
h.3 ASCII Commands No Type Description Command Argument 1 Argument 2 Argument 3 Argument 4 Return string 1 Set Full Scale Flow FF in SLPM CHANNEL VALUE 1 char. [1-4] float [0-99999.0] FF CHANNEL VALUE K[CR][LF] Ex: FF 4 10.0 [CR][LF] 2 Set current Engineering Units INDEX: 0 - % F.S. CHANNEL 1 char.
No Type Command Argument 1 Argument 2 Argument 3 Argument 4 Return string Single Data SD Request Returns a string containing readings in %F.S. for all available channels. NON String with current reading in %F.S for all channels. If channel not calibrated [*] will be added to the reading. Turns ON/OFF the 16 bit check sum transmission of check sums with the data packet. MODE: 0 - OFF 1 - ON Set TOTALIZER start FLOW in %F.S.
No Type 2 2 2 3 2 4 RELAYS ASSIGNMENT AND STATUS 2 1 ALARM SETTINGS AND STATUS COMMANDS 2 0 2 6 BATCH SETTINGS 2 5 TIMER SETTINGS 2 7 2 8 2 9 Description Command Argument 1 Argument 2 Argument 3 Argument 4 AH CHANNEL 1 char. [1-4] Read ALARM STATUS Returns: 0 - NO ALARM 1 - HIGH ALARM 2 - LOW ALARM AS NON AS ST ST[CR] [LF] Ex: AS 0 2[CR][LF] (example above for two channels SDPROC) ALARM Status SCA command.
No Type Description Command Argument 1 Argument 2 Argument 3 Argument 4 Return string General status SCF command #1 Returns: Instrument model, TCP/IP flag, Full scale flow in SLPM, Current E.U For all available channels. General status SCS command #2 Returns: Reference, Valve mode, Set Point For all available channels. NON 32 Set Instrument IP IPC ADDRESS**IP address string must have decimal notation (example: 198.192.1.104) maximum 15 characters are allowed. IP ADDRESS String: XXX.XXX.XX X.
No Type Description Command Argument 1 Argument 2 Argument 3 Argument 4 Return string Read current Name NSS Server IP address** NON Device Name Server: .85.127. 15 64.85.127.55 [CR][LF] 40 Set User Name and UAC User Password** User NAME User (max. 10 Password characters) (max. 10 characters) NON UAC user password OK[CR][LF] Domain Host Name Name (max. 25 (max.
(i) Network Communication Interface (optional) i.1 10Base-T RJ-45 Pinout The optional 10Base-T Ethernet network (RJ-45) system is used in the SDPROC for network connectivity. The 10 Mbps twisted-pair Ethernet system operates over two pairs of wires. One pair is used for receiving data and the other pair is used for transmitting data. Total four pins of the eight-pin connector is used.
i.2.2 DNS DNS, Domain Name System enables individual computers and devices to be recognized over the network base on specific name instead of an IP address. For example, instead of having to use http://192.168.1.19 (which is device IP address), we can use only http://sdproc or any eight characters name stored as the Host Name in the SDPROC. By default each device shipped with Host Name: sdproc.
Figure i-2 Pinging SDPROC MS-DOS Prompt i.4 Operation Using the SDPROC Web Page a) b) c) Start your Web browser. From the browser type http://192.168.1.19 (if IP address was changed use new IP address). The Home Page, shown below, will be displayed. Figure i-3 Network Password Page d) Enter User Name and Password and click OK. The SDPROC is shipped with default User Name: “user” and Password: , NOTE: “password”.
Once you are done with the user Name and Password, the Home Page, shown below, will be displayed. Figure i-4 Using SDPROC with Telnet Console Figure i.4 SDPROC control Page You can type the number of the channel you want to monitor or control. You can also enter the desired value of the set point. From the drop-down window you can select the valve control mode for the mass flow controller.
(J) TROUBLESHOOTING J.1 Common Conditions Your SDPROC Command Module was thoroughly checked at numerous quality control points during and after manufacturing and assembly operations. It was calibrated in accordance to your desired conditions and options. It was carefully packed to prevent damage during shipment.
J.
APPENDIX 1 COMPONENTS DIAGRAM SDPROC MAIN PC BOARD 48
APPENDIX 2 DIMENSIONAL DRAWING SDPROC COMMAND MODULE 49
APPENDIX 3 WARRANTY Aalborg7 Mass Flow Systems are warranted against parts and workmanship for a period of one year from the date of purchase. Calibrations are warranted for up to six months after date of purchase, provided calibration seals have not been tampered with. It is assumed that equipment selected by the customer is constructed of materials compatible with gases used. Proper selection is the responsibility of the customer.