Installation Instructions
 Installation and Service Manual Upsilon-Series 
42
Vent
Prog.
OK
-
+
OK
-
+
9.5 Fillingtheheatingsystem
When  all  boilers  have  been  electrically  commissioned  as  described  above,  then  the  
heating system can be lled. Each boiler is tted with a lling and drain valve. The lling 
hose from the water tap is then connected to it.
Filltheheatingsystemonlywithdrinkingwater.RefertotheWaterQualitychapter
forqualityrequirementsofthellingwater.
Waterpressure
Screen display
Good
Read-out
Operation
status
Technical 
read-out
Description Action
FILLdd 
00:00
FILL
Bx12sc03
xx.x°C
P0,0
Water pressure is 0 bar, boiler off Top up water
FILL
dd 00:00
FILL
Bx12sc03
xx.x°C 
P>0,7
Water pressure above 0.7 bar. The boiler 
is off. The automatic venting program 
starts
Top up water until 
approx. 1,7 bar
Block.
dd 00:00
Vent
Prog.
xx.x°C 
P>1,2
Automatic venting program, afterwards 
(approx. 13 min.) boiler is on standby
Top up water until 
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C 
P>1,0 <4,0
Water pressure is good. Boiler standby or 
in normal operation
None
Block.
dd 00:00
xx.x°C 
P>4,0
Water pressure too high, boiler off due to 
blocking
Drain water until 
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C 
P<3,7
Water pressure is good. Boiler operates 
normally again
None
Message/
Block.
dd 00:00
FILL
Message
Mx24sc14
xx.x°C 
P<1 >0,7
Water pressure too low. Boiler is limited 
to 50% load
Top up water until 
approx. 1,7 bar
Ventingprogram
When, on lling the system, the water pressure rises above 0.7 bar, the venting program 
will start automatically. The program  lasts  approx.  13 minutes and in doing so, turns 
the pump on and off and, if tted, the three-way valve every 80 seconds to remove the 
remaining air from the boiler. All venting points still have to be vented when lling the 
installation. The boiler will be on standby after the venting program.
Theautomaticventingprogramonlyventstheboilerandnottherestoftheinstal-
lation.
Read-out 1 (Good status) displays Block. with actual day and time on the screen. 
Read-out 2 (operational status) displays Vent Prog on the screen. [From Good press  
the – button 1x: Vent Prog is now displayed]
Interrupting the venting program (not recommended) is only possible from the setting 
level by pressing OK during the venting program.
For boiler checks please refer to the chapter Checks prior to commissioning. 
For any checks or setting changes, refer to the Basic Settings chapter.
  FILL
Block.