*Foreach90degreeelbowadded,deduct5ft.frommax.vent
4.INSTALLATION
Theseguidelinesarequickoverviewsonthemainpointsofinstallation–Forallinstallationdetails,refer
tothe520(T‐H2)or320(T‐H2S) InstallationManualthatispackagedwitheveryheater.Followallcodes
pertainingtotheinstallationofagasappliance.
VENTING
OUTDOORMODELIN STALLATION:
•  OutdoorinstallationsfallundertheDirect VentClearancespublishedbyANSIZ223.1/NFPA54or
CAN/CSA‐B149.1
•  Choosealocationthatmeetsallclearancesrequiredbycode.Thetwomostcommonare:
o  1ft.fromanyopeningintothebuilding,e.g.doors,windows,etc.
o  Thetopmustbe
atleast3ft.belowasoffit,ventilatedornon‐ventilated,orbelowan
overhang.
INDOORMODELINSTALLATION:
•  Refertothefollowingtableforventinglengthmaximums:
Table2
Diameter Max.No.ofElbow Max.Vertical&Horizontal(Total)VentLength
3” 2 25ft.
4” 5 50ft.
•  TheventingmayconsistofSchedule40PVC,CPVC,ABS,orCategoryIIIStainlessSteel.
•  InCanada,PlasticventingrequiresULCS636Certifiedmaterials.
•  DirectVentcombustionairintakeisveryimportant.
o  InstalltheDirectVentairintakeopeninginanareathatisfreeof
airbornedebris(lint,
grease,dust,flammableliquids,vapors,orchemicals).Dirtyburnertrayandsensorsare
averycommoncauseoftheheateroperatingimproperly.
o  Freshairintakepipingmaybemanifoldedusingthefollowingequation:
(newventcross‐sectionalarea)=(numberofheaters)x(5.65)
DONOT:
o  Commonventtheexhaustofanytanklessheaterwithanyotherheaterorvented
appliance.
o  Terminatetheexhaustintoachimney.Anexistingchimneymaybeusedasachaseto
runexhaustpipeallthewayupandterminatetotheoutside.
o  Reduceorincreasethe
ventpipediameterbeyondwhatisspecifiedintheinstallation
manual.