Specifications

TroubleshootingGuide
22|Page
5.4TROUBLESHOOTINGPROCEDURES
VerifyingproperDipswitchsettings p.22
Drainingtheunit p.23
Cleaningthefilter p.23
CheckingforaCrossConnection p.24
CheckforReverseConnection p.24
Checkgassupplypressure p.24
Purgethegaslineofair p.24
Adjustingmanifoldpressure p.25
ResettingtheComputerBoard p.26
CheckingtheOHCF p.26
VERIFYINGPROPER
DIPSWITCHSETTINGS:
IncorrectDipswitchsettingscancausea031
errorcode.
Table4LeftBankofDipswitches
No. Function ONposition OFFposition
1 Gastype Propane Disable
2 NaturalGas Disable
3 N/A N/A N/A
(Default)
4 Allowadjustmentsoffanmotorspeed
(Similarproceduretochangingmanifoldpressure)
Enable Disable
(Default)
5 FM+,FM++,FM+++
Fanmotorforcombustion
No.5
OFFposition ONposition
No.6 OFFposition 0% +6%
ONposition +12% +18%
Fanmotorforexhaust(Indoormodelsonly)
 No.5
OFFposition ONposition
No.6 OFFposition 0% +3.6%
ONposition +7.3% +11.4%

6
7 INPUT‐(Maximumgasinputisreduced) 10%Max
Input
Disable
(Default)
8 Allowaccesstooperationhistory
(Specialpurposeonly)
EEPROMdata
transfer
Disable
(Default)
9 N/A N/A N/A
(Default)
10 Typeofwaterheatermodel Indoor Outdoor
Figure23