Installation Guide
INSTALLATION
Electric Tankless Water Heater •      11
INSTALLATION
Getting Started
 Clearances
See Figure 1 or Figure 2. 
Top Clearance: A minimum of 12 
inches (30.5 cm) is required for 
removal and maintenance of heating 
elements and to provide access for 
plumbing connections.
Side Clearance: Allow an 8 inch (20.3 cm) 
minimum horizontal space for the 
heater. This horizontal clearance will 
allow for the removal of protective 
cover screws and provide access to 
electrical wires that will enter the 
heater from the side.
Bottom Clearance: At a minimum, 
maintain a bottom clearance of 8 
inches (20.3 cm) for single chamber 
models or 15 inches (38.1 cm) for 2- or 
4-chamber models. Do not store any 
items underneath the water heater.  
Front Clearance: Maintain a minimum 
clearance of 8 inches (20.3 cm). In the 
absence of a door or removable access 
panel in front of the heater, allow a 
minimum of 15 inches (38.1 cm) front 
clearance. This will allow for cover 
removal and ease of service. See 
Figure 1 or Figure 2.  
Code Compliance
•  Install and properly ground the 
unit in accordance with local 
codes, or in the absence of local 
codes, with the current edition 
of the National Electrical Code: 
ANSI/NFPA 70 in the USA or 
CSA standard C22.1 Canadian 
Electrical Code, Part 1 in Canada.
•  Follow all other applicable 
plumbing, heating, and air 
conditioning codes during 
installation.
1
Choose a 
Location
•  Your water heater is designed to 
be installed indoors only.
•  Locate your water heater in a 
clean, dry area that is as close to 
the point of use as possible. Do 
not install it in a bath enclosure or 
shower stall. 
•  Your water heater and water lines 
must be protected from freezing. 
Do not install your water heater 
where it may be subjected to 
freezing temperatures.
•  Avoid locations that are prone 
to dampness, high humidity, 
moisture, or dust. Such locations 
include crawl space under a house 
or building, in the garage (in 
regions prone to high humidity) 
and in the attic (unless the attic 
has been converted to a living 
space). 
•  Locate your water heater where it 
will not be accessible to children.
 WARNING!  This water heater 
can make water hot enough to 
cause severe burns instantly, 
resulting in severe injury or death.
•  Be sure that your water heater 
is accessible and that minimum 
Wall or 
adjacent 
object 
12”
(30.5 cm)
15”+
(38.1 cm +)
2-Chamber or 
4-Chamber 
Water Heater 
Minimum Clearances
8”
(20.3 cm)
8”
(20.3 cm)
°F
°C
ENTER
Front 
View
Side View
Wall
Front Clearance:
15” + (38.1 cm +)
Install one
ƐƚĂŶĚŽīďƵŵƉĞƌĂƚ
each corner. 
;ϰƚŽƚĂů͖ƉƌŽǀŝĚĞĚ͘Ϳ
Figure 1.  
Side View
Wall
Wall or 
adjacent 
object 
12”
(30.5 cm)
8”+
(20.3 cm +)
Front Clearance:
15” + (38.1 cm +)
Single 
Chamber
Water Heater
Minimum Clearances
8”
(20.3 cm)
8”
(20.3 cm)
Front 
View
Figure 2.  
NOTICE: Point-of-use models may be mounted 
horizontally. See Figure 3, page 12. 
Maintain 12” (30.5 cm) MIN. clearance at 
inlet/outlet.)