Installation Guide
17 Page
-Clearances for sidewall terminaons-
-Clearances for rooop terminaons-
Multiple-unit, concentric wall 
terminals: Space each concentric 
wall terminal at least 1 ft (30 cm) 
away from each other, no matter 
the orientation. A concentric wall 
terminal must also be at least 2 ft 
(61 cm) away from an inside corner.  
If the adjacent wall is less than 2 
ft (61 cm) of length, the minimum 
required distance away from the 
inside corner will be equal to the 
length of that adjacent wall.
Concentric wall terminals 
should be at least 2 ft (61 
cm) away from an opposite 
surface/wall. Do not place the 
termination directly in front of 
an opening into a building.
Concentric wall 
terminals should be at 
least 3 ft (91 cm) away 
from a ventilated or 
unventilated soffit.
Installaon
Installaon Manual
Inside
corner
Anticipated snow level
1 ft
(30 cm)
min.
2 ft
(61 cm)
min.
1 ft (30 cm)
min.
2 ft
(61 cm)
min.
3 ft
(91 cm)
min.
Improper installation can result in carbon monoxide poisoning or death. Follow all local 
and national codes in regards to proper termination clearances. In the absence of such 
codes, the clearances below can be used as guidelines. Local codes supersede these 
guidelines.
WARNING
Canadian requirements differ from the guidelines in this section. In Canada, follow 
the requirements of B149.1 (Natural Gas and Propane Installation Code, current 
edition) as well as local and provincial codes. Contact your local code enforcement 
agency for direction.
NOTICE
Angled roof termination
Intake air
Intake air
Exhaust
gas
Exhaust
gas
5 ft (152 cm) min.
1 ft
(30 cm)
 min.
1 ft
(30 cm)
 min.
Anticipated
 snow level
Flat roof termination
Intake airIntake air
Exhaust
gas
Exhaust
gas
2 ft (61 cm)
min.
1 ft
(30 cm)
min.
Anticipated
snow level
2 ft (61 cm) min.
1 ft
(30 cm)
min.
Vertical
wall
 Minimum spacing between multiple concentric terminals for rooftop:
 On the same level: 2 ft (61 cm) spacing between each
 On the different level: 5 ft (152 cm) spacing between each
 The exhaust termination must be a horizontal distance of at least 2 ft (61 cm) from a wall 
or surface unless specified differently by local code.
 Failure to observe this warning may result in severe personal injury or death.
WARNING
1 ft
(30 cm)
min.