Installation Guide
Residen al Standard Gas Water Heater Use and Care Guide • 9
GETTING STARTED
Residen al Standard Gas Water Heater Use and Care Guide • 9
GETTING STARTED
A2: Calculate required air volume
A water heater installed in an unconfi ned 
a  c or garage requires that the space 
be at least 50 cubic feet per 1,000 BTU/
HR of the total input for all gas burning 
appliances in the same area.
[Total BTU/HR/1000] x 50 = Cubic feet 
of air required.
Example: 
(135,000 / 1000) x 50 = 6,750
If the air volume of the room is less 
than the required air volume, you must 
provide two permanent outside air 
openings that draw in suffi  cient air. Use 
Op on B. 
If the air volume of the room is greater 
than the required air volume, it may 
be possible to install the water heater 
without outside ven la on. 
A3: Check that combus on ven-
 la on is adequate
Because modern homes are o en well-
sealed to prevent dra s, even a large 
room may not provide enough combus-
 on air without ven la on. To con-
fi rm that your installa on has enough 
combus on air, conduct the vent dra 
test on pages 23-24 when installa on is 
fi nished. 
Op on B: Install with outside 
ven la on
Ven la on with outside air is recom-
mended, and, for most installa ons, is 
needed. There may be exis ng ven la-
 on that is adequate, or you may need 
to add more ven la on.
Supplying outside air to typically requires 
two openings. One opening must be 
within 12 inches from the fl oor and 
the second opening must be within 12 
inches from the ceiling. Although a single 
opening is not preferred, you may use a 
single opening to outside air if the mini-
mum free area is sized according to Table 
3. Two openings must be used when 
ven la ng with air from another room.
The outside air can be taken from a 
crawl space or a  c open to the out-
doors and adequately ven lated. You 
may use ver cal or horizontal ducts. 
B2: Determine type of ven la-
 on
There are several types of ven la on 
that can be used :
1.  Direct to outdoors
2.   Ver cal ducts
3.   Horizontal ducts
4.   Single opening (not recom-
mended; must be at least 100 
square inches. Not appropriate 
for confi ned spaces smaller than 
50 cubic feet per 1,000 BTU/HR as 
calculated in sec on A or when 
ge  ng air from another room.)
5.  From a larger room inside the 
house (not recommended – refer 
to sec on A above to determine if 
the combined volume of the rooms 
may be adequate).
B3: Determine minimum free 
area required for each vent 
opening
The size of the vent openings depends 
on the total BTU/HR ra ng of all appli-
ances in the space (use your calcula on 
from “Before beginning”) and the type 
of vent used. Table 3 provides the mini-
mum free area for each vent opening 
depending on the type of ven la on.
B4: Calculate minimum size of 
vent openings and ducts
The vent cross-sec onal area needed to 
provide the free area depends on the 
covering on the vent openings. Typical 
vents use louvers or grilles to protect 
the opening. The louver or grill itself 
blocks some of the free area, so the 
opening may need to be larger to meet 
the minimum free area requirements. 
Use the following formula to calculate 
the required cross-sec onal area:
Cross-sec onal area = minimum free 
area required ÷ percent free area of 
Table 3
Minimum Free Area of Permanent Openings for Ven la on and Combus on Air 
Supply – All Air from Outdoors Only.
Based on the total BTU/HR input ra ng for all gas burning appliances within a 
confi ned space.
Opening Source  Minimum Free Area 
  Per Opening (sq. in.) 
*Direct to outdoors  1 sq. in. per 4,000 BTU/HR (see fi gure on page 10) 
Ver cal ducts  1 sq. in. per 4,000 BTU/HR (see fi gure on page 10) 
Horizontal ducts  1 sq. in. per 2,000 BTU/HR (see fi gure on page 10) 
Single Opening  1 sq. in. per 3,000 BTU/HR (see fi gure on page 10) 
*These openings connect directly with the outdoors through a ven lated a c, a 
ven lated crawl space, or through an outside wall.










