Operation Manual
14
User Manual Epsilon-Series
Selection
Type of installation
Flow water
temperature
01
Radiators; air heating; convectors 85°C
02
Radiators with large surface areas or under floor heating as
additional heating
70°C
03
Under floor heating with radiators as additional heating 60°C
04
full under floor heating 50°C
= factory setting
Adjusting the type of installation
The boiler is designed in such a way that it will
adjust itself automatically to what is necessary
for a normal heating system. In some cases the
installation may have convectors or complete un-
deroor heating.
One can easily choose heating installation adjust-
ments appropriate for the system such as maxi-
mum water-ow temperature or for the warming up
of the installation after a night period. Adjustment
goes as follows:
- Press (from the Technical) reading the Mode
key once;
- Press the Step key twice;
The display will show 2 01.
- Press the + or the - key to alter the type of
installation according to the table below;
- Press the Store key to conrm the setting;
The display will ash once.
- Press the Mode key once;
The display will show StbY for a short while
and will return to the Technical reading.
+
Store
Mode
Step
Reset
-
When a type of installation has been chosen with a low water-ow temperature it
is possible that in case of a severe winter period the temperature of the heating
system will need to be increased slightly. In such situations the installation choice
may need to be changed, so that a higher ow temperature can be chosen. This
adjustment would normally be carried out by your installer during the installation
and commissioning.










