Installation Instructions
Installation and Service Manual Epsilon-Series
21
6.7.1 Dimensioning of the ue gas and air intake duct
The ue diameter is determined by the total length of the run, including for the connection
pipe, elbows ttings and terminal covers etc. and the type and number of boilers installed
into the system.
An undersized ue pipe can lead to disorders. Look at table 6.7.1.a for the choice of the
system and the correct diameter. The table below shows the maximum ue lengths with
the dierent boiler outputs. A longer ue gas length can be achieved by increasing the
diameter to ø 100mm.
Explanation table 6.7.1.a:
Parallel ue gas system: maximum noted length = distance between boiler and roof
terminal A
Concentric ue gas system: maximum noted length = distance between boiler and roof
terminal B
When using bends the noted value behind every bend should be deducted from the
maximum straight length.
ø80mm
A
in m
ø100mm
A
in m
EB 40 Maximum straight length 80 18 Maximum straight length 100 39
87° bend resistance length -1,4 87° bend resistance length -2,1
45° bend resistance length -0,9 45° bend resistance length -2
EB 50 Maximum straight length 80 6 Maximum straight length 100 18
87° bend resistance length -1,4 87° bend resistance length -2,1
45° bend resistance length -0,9 45° bend resistance length -2
ø80/125mm
B
in m
ø100/150mm
B
in m
EB 40 Maximum straight length 80/125 13 Maximum straight length 100/150 34
87° bend resistance length -3 87° bend resistance length -1,7
45° bend resistance length -1,9 45° bend resistance length -1,3
EB 50 Maximum straight length 80/125 6 Maximum straight length 100/150 10
87° bend resistance length -3 87° bend resistance length -1,7
45° bend resistance length -1,1 45° bend resistance length -1,3
Parallel flue system
Concentric flue system
Dimensionsuegassystemandairsupplysystem Table6.7.1.a
Example:
A EB 40 with a concentric
ue gas system ø80/125mm
has according to the table a
maximum ue straight length
of 13m In the system that is
going to be put in there are
2 x 45° bends, so the
maximum ue gas length
is
13 – ( 2 x 1.9 ) = 9.2 meters.