Final discharge options.
The condensate pipe can only terminate into any one of the ve areas as shown in the
gures on this page.
Draining of the condensation water to the external rain guttering is not
permitted in view of the danger of freezing.
Before putting the boiler into operation ll the syphon with 600 ml of
water.
A -Condensate from boiler syphon/trap
B -Sink with internal overow
C -25mm dia. Plastic condensate pipe
D -External drain or gully
E -Internal soil and vent stack.
F -Serviceable condensate trap (75mm min.)
G -300mm x 100mm dia. sealed plastic tube.
H -Ground level
J -Drainage holes facing away from the building
K -Lime stone chippings
L -Weather resistant insulation
Drainrequirements gure6.6.b