- Should you wish to achieve the required water quality by using chemical addi-
tives, then this is your own responsibility. The warranty on the product delivered by
A.O. Smith expires, if the water quality does not meet A.O. Smith's specications or
the chemical additives have not been approved by A.O. Smith.
- On installation and during additions or changes at a later stage, A.O. Smith recom-
mends to keep a record of the type of water used, its quality at the time, and if ap-
plicable, which additives and quantities were added.
Parameter Value
Water type Potable water
Softened water 6.0-8.5
pH 6.0-8.5
Conductivity (at 20°C in µS/cm) Max. 2500
Iron (ppm) Max. 0.2
Hardness (°dH)
Installation volume/capacity 1-7
<20 l/kW 1-12
Installation volume/capacity Refer to Additives Attachment
>=20 l/kW 1-7
Oxygen No oxygen diusion allowed during ope-
ration.
Max. 5% lling water addition annually Refer to Additives Attachment
Corrosion inhibitors Refer to Additives Attachment
pH increasing or lowering agents Refer to Additives Attachment
Anti-freeze additives Refer to Additives Attachment
Other chemical additives Refer to Additives Attachment
Solid substances Not allowed
Residues of processing water not for-
ming part of the drinking water
Not allowed
table 6.3.a
Water type denition:
Potable water: Tap water compliant with the European drinking water guideline:
98/83/EG dated 3 November 1998.
Softened water: Water with partly de-ionised calcium and magnesium.
Demi-water: Virtually completely demineralised water (very low conductivity)
Distilled water: Water no longer containing minerals.