Unit installation
8
LOCATING THE HEATER
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES
SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR
OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE
LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE
STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS
ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE
IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES
CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES
PERMIT OPERATION OF GAS APPLIANCES IN SUCH AREAS
IF THEY ARE INSTALLED 18” (.50m) OR MORE ABOVE THE
FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH
AN AREA CANNOT BE AVOIDED.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A
CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead
the water heater must be placed on a metal or wood panel
extending beyond the full width and depth by at least 3 inches
(7.6cm) in any direction. If the heater is installed in a carpeted
alcove, the entire floor shall be covered by the panel. Also, see
the DRAIN REQUIREMENTS.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING
VEHICLE.
WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER.
OPEN CONTAINERS OR FLAMMABLE MATERIAL SHOULD
NOT BE STORED OR USED IN THE SAME ROOM WITH THE
HEATER.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack or
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD
BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE
HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE
TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.
Such pans should be fabricated with sides at least 2" (5cm) deep,
with length and width at least 2" (5cm) greater than the diameter
of the heater and must be piped to an adequate drain. The pan
must not restrict combustion air flow.
For appliance installation locations with elevations above 2000
feet (610m), refer to HIGH ALTITUDE INSTALLATIONS section
of this manual for input reduction procedure.
LEVELING
If the unit is not level, insert the bolts which were used in crating
into the legs to correct this condition.
CLEARANCES
These heaters are approved for installation on combustible flooring
in an alcove when the minimum clearance from any combustion
construction are followed as indicated in figure 6 and Table 1.
The following units are approved for installation with side, rear
and ceiling clearances as indicated below:
A
)EDISTHGIR(
B
)EDISTFEL(
C
)KCAB(
D
)GNILIEC(
021
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
451
)mc45.2("1)mc5.2("1)mc5.2("1)mc84.03("21
081*
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
791*
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
891
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
991*
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
002
)mc45.2("1)mc45.2("1)mc45.2("1)mc84.03("21
052
)mc80.5("2)mc80.5("2)mc80.5("2)mc84.03("21
152
)mc80.5("2)mc80.5("2)mc80.5("2)mc84.03("21
572
)mc80.5("2)mc80.5("2)mc80.5("2)mc84.03("21
503
)mc80.5("2)mc80.5("2)mc80.5("2)mc84.03("21
563**
)mc57.7("3)mc57.7("3)mc57.7("3)mc84.03("21
004
)mc57.7("3)mc57.7("3)mc57.7("3)mc84.03("21
005
)mc7.21("5)mc7.21("5)mc7.21("5)mc08.05("02
raerdnasedisot)mc80.5("2asahnoisrev)C(RTBehT*
raerdnasedisot)mc61.01("4asahnoisrev)C(RTBehT**
TABLE 2
In all installations the minimum combustible clearances from any
draft hood surface or vent piping shall be 6" (16cm). Vent piping
passing through a combustible wall or ceiling must be a continuous
run (no joints) and retain the 6" (16cm) clearance unless an
approved reducing thimble is used.
A service clearance of 24" (61cm) should be maintained from
serviceable parts, such as relief valves, flue baffles, flue damper
devices, thermostats, cleanout openings or drain valves.
HARD WATER
Where hard water conditions exist, water softening or the threshold
type of water treatment is recommended. This will protect the
dishwashers, coffee urns, water heaters, water piping and other
equipment.
See MAINTENANCE section for details of tank cleanout
procedure.
AIR REQUIREMENTS
REFER TO THE LATEST EDITION OF THE "NATIONAL FUEL
GAS CODE" ANSI Z223.1/NFPA 54. FOR CANADA CONSULT
CAN/CGA B149.1 OR .2.
KEEP APPLIANCE AREA CLEAR AND FREE OF
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLES, VAPORS AND LIQUIDS.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.










