Operating Instructions and Installation Instructions

BMS Interface Module
Para-
meter
Register
type
Value Type Unit Description
Conversion
y = first byte
x = second byte
Unit type
BFC SGS SGE
31 03 16 bits direct Temperature °C Solar return temperature of the Q/T sensor (S4) x/100 n.a. Yes
Yes
32 03 16 bits direct Temperature °C Temperature limit for solar heating x/100 n.a. Yes
Yes
33 03 16 bits direct Contribution Watt Solar contribution; actual - n.a. Yes
Yes
34 03 16 bits direct Contribution MJ Solar contribution; last 24h - n.a. Yes
Yes
35 03 16 bits direct Contribution GJ Solar contribution; total - n.a. Yes
Yes
36 03 16 bits float Flow l/min Actual flow through the Q/T sensor - n.a. Yes
Yes
37 03 16 bits direct Solar pump % Modulation percentage of the solar pump
x/2.55
(0…100% = 0…255)
n.a. Yes
Yes
38 03 16 bits direct Warning ON/OFF Warning Service required ON 1=On, 0=Off Yes
Yes
Yes
39 03 16 bits direct Day Anti legionella purge; day
Sun (=0) … Sat (=6)
Legionella off = 7
Yes
Yes
Yes
40 03 16 bits BCD Time Hh:mm Anti legionella purge; start time y=hh, x=mm Yes
Yes
Yes
41 03 16 bits BCD Time Hh:mm Anti legionella purge; end time y=hh, x=mm Yes
Yes
Yes
42 03 16 bits direct Temperature °C Anti legionella purge; set point x/100 Yes
Yes
Yes
43 03 16 bits direct Error - Actual error solar system (internal code) - n.a. Yes
Yes
44 03 16 bits direct Warning ON/OFF Warning Anode ON 1=On, 0=Off Yes
Yes
Yes
45 03 16 bits direct Heat input % Actual heat input in % of the maximum load
x/2.55
(0…100% = 0…255)
Yes
Yes
Yes
46 03 16 bits direct Relay - Relay: Error activated 1=Closed, 0=Open Yes Yes
Yes
47
48
49
50