FOR YOUR SAFETY, READ BEFORE INSTALLATION:
Do not install the water heater or vent
termination next to a dryer or dryer vent. The
water heater environment must be free from
any source of airborne debris that can be
trapped inside the water heater.
Installaon
Installaon Manual
Water heater vent terminator must be at least 2 ft.
(61 cm) away from an inside corner.
WARNING FOR INSTALLATIONS
• Do not install the water heater and its termination where water,
debris or flammable vapors may get into the water heater and
flue terminal. This may cause damage to the heater and void the
warranty.
• Do not have the vent terminal pointing toward any opening into a
building.
• Do not locate your heater in a pit or location where gas and water
can accumulate.
Prohibited
1 . (30 cm) min. USA
3 . (91 cm) min. Canada
1 . (30 cm) min. USA
3 . (91 cm) min. Canada
1 . (30 cm) min. USA
3 . (91 cm) min. Canada
12-inches (30.48 cm) above grade
or ancipated snow level
Ancipated snow level
Do not install the water heater vent
terminator within 1 ft. (30 cm) in
the USA of any air intake or building
opening, and within 3 ft. (91 cm) in
Canada of any air intake or building
opening.
Inside
corner
2 ft.
(61 cm)
min.