Specifications
8
stcudorP retaW htimS .O .A Service Workbook
Ashland City, Tennessee 2005© Training Department
MULTI-VENTING CONFIGURATIONS
GENESIS 1000-2500 MODELS
Horizontal Sidewall Direct Venting Rear
Intake/Exhaust
Vertical Direct Venting Top Exhaust
Horizontal Venting With Vertical
Combustion Air Intake Top Intake/Rear
Exhaust
Horizontal Sidewall Venting Rear Exhaust Conventional Vertical Venting Top Exhaust
Horizontal Venting With Horizontal
Combustion Air Intake Rear Intake/Top
Exhaust
Venting Options for The Genesis:
May be vented from the top or rear of the unit.
May be vented vertically or horizontally.
May use room air or be direct vented. (Air intake is on rear of cabinet only.)
Vertical vent, non-direct is Category I. May be common vented - Barometric Draft Control required.
Horizontal vent and direct vent are Category III. May NOT be common vented with other appliances.
Use Barometric draft
Regulator to maintain
-.02 to -.04 draft if
necessary.