TROUBLESHOOTING ERROR CODES
Error Code "030" - This indicates that the Flow Switch is not closed.
On Display Board red light is on "Circulation Fail" Red indicates LED - On
Display Window will show "LOCO 030".
Power is "ON" - Plugs are in receptacles
Central Control Board
Lockout
Status
If error code is
then
check connection and 24V hot from CCB CN13, Pin 1 to TB3,
Terminal 25.
check connection and 24 VAC hot from TB3, Terminal 25 to TB1,
Terminal 8.
check connection and 24V hot from TB1, Terminal 8 to Flow Switch.
if flow switch is closed, TB1, Terminal 7 to Ground should be 24V.
check connections from TB1, Terminal 7 to CCB CN13, Pin 7.
replace wiring, check board Flow Switch and paddle as required.
check connections (Amp) for c
onduit assembly
"030" indicates Circulate Fault (Flow Switch)
030Soft