Specifications
29
A. O. Smith Water Products Service Handbook
Ashland City, Tennessee 2005
©
Training Department
IGNITION CONTROL BOARD
1 PER STAGE
Each ICB is responsible for a:
• combustion blower
• hot surface igniter
• gas valve
Each ICB will monitor:
• a gas valve
• gas valve relay
• flame sense
• igniter current
Each ICB has changeable jumpers (J24) to provide a unique communication address. Jumpers,
J26, J27, also allow the user to disable the igniter and/or blower if they are not connected to the
ICB. These jumpers also allow selection of 1 or 2 blower speed operation (not used on these
Genesis models). See Page 31.
Flame
Sensor
Hot
Surface
Ignitor
(HSI)
24 VAC
Transformer
Combustion
Blower
Line
Voltage
Gas
Valve
Board to
Board Gas
Valve
Power
To Next
Stage ICB
From
Previous
Stage ICB
(To and from
connections
are
interchangable)
J24
J26
J27
(Inside, Around Walls of Cabinet)
1 Board per stage (3 or 4)