Product specifications

AD-4329A Weighing Indicator Page 39
9.3. Setpoint Comparison
This function includes the weighing sequence and uses for getting preset target
weight.
There are four parameters of "Final", "Preliminary", "Free fall" and "Zero band" to
use the setpoint comparison.
The result of the sequence is output to three relays.
When inputting these parameters, it is not necessary to input the F-function f-20
again unless changing the F-function.
Caution This function is normal batching only and can not perform
loss-in-weight.
9.3.1. Selecting Setpoint Comparison
Step 1 Press the
Operate/Standby
key to turn display off.
Press and hold the MODE key and press the
Operate/Standby
key to enter the F-function mode.
Step 2 Select f-20 2 (setpoint comparison).
Step 3 Turn the display off using the
Operate/Standby
key.
9.3.2. Description of Input parameters and Outputs
Output and Condition
Parameters List
SET0 Final Set a preset target weight.
SET1 Free fall Set a corrective value related to closing the dribble flow gate.
SET2 Preliminary Set a begining point to use the dribble flow gate only.
SET3 Zero band Set a value to regard as nearly zero.
9.3. Setpoint Comparison