Specifications

31
When connecting to an external device with hardware flow control, communication
will be impossible using a cable without RTS and CTS connected. In that case,
connect RTS and CTS. This will disable hardware flow control, but will enable
communication.
When the connector of an external device is a D-Sub 9-pin connector, pin 7
is RTS and pin 8 is CTS.
When the AX-KO3285-320 cable is used, RTS and CTS are internally
connected and the above operation is unnecessary.
14.2.2. SW-03 specifications
RS-232C interface
Transmission form Asynchronous, bi-directional, half-duplex
Data format Baud rate: 2400, 4800, 9600 bps
Data bits: 7 bits + parity 1bit (EVEN / ODD)
or 8 bits (non parity)
Start bit: 1 bit
Stop bit: 1 bit
Code: ASCII
Terminator: C
R
L
F
(C
R
:0Dh, L
F
:0Ah)
LSB
0
1
2
3
4
5
MSB
6
Relay output
The maximum rating of the replay output is as follows.
Maximum voltage: 50V DC
Maximum current: 100 mA DC
Maximum ON resistance: 8
Sto
p
bit
1 (-15V~-5V)
0 (5V~15V)
Start bit
Data bi
t
s
Parity bit