Product specifications
Page 40 AD-4402
7.3.1.
7.3.1.7.3.1.
7.3.1. N
NN
Normal
ormal ormal
ormal B
BB
Batching of Built
atching of Builtatching of Built
atching of Built-
--
-in automatic
in automatic in automatic
in automatic
program mode
program modeprogram mode
program mode
Normal batch weighing weighs the material charged into the hopper.
Control gates (valves) can be used. (Full flow, medium flow and dribble flow)
Concerning Parameters of the Function
Selecting normal batching of built-in automatic program mode.
[5q f- 1] [2] Built-in automatic program mode
[Function] - [Function setting] - [Sequence] - [Basic] - [Weighing mode]
[5q f- 3] [0] Normal batch weighing
[Function] - [Function setting] - [Sequence] - [Basic] - [Loss-in-weigh]
Setting the display to automatically when starting the sequence.
[5q f-11]
[Function] - [Function setting] - [Sequence] - [Control] - [Batch start settings]
Preventing vibration due to gate operation.
[5q f-33]
[Function] - [Function setting] - [Sequence] - [Timer] - [Full flow comparison
interrupt timer]
[5q f-34]
[Function] - [Function setting] - [Sequence] - [Timer] - [Medium flow
comparison interrupt timer]
[5q f-35]
[Function] - [Function setting] - [Sequence] - [Timer] - [Dribble flow
comparison interrupt timer]
Sending an alarm signal when the sequence time over is.
[5q f-31] Maximum weighing time between start and batch finish can be set.
Error code [SQ.ERR 4] is displayed, when an error occurs.
[Function] - [Function setting] - [Sequence] - [Timer] - [Batch monitoring
timer]
Removing "stable" from comparison condition.
[5q f-13]
[Function] - [Function setting] - [Sequence] - [Control] - [Eval condition]
Changing the timing of comparison.
[5q f-37]
[Function] - [Function setting] - [Sequence] - [Timer] - [Eval delay timer]
Changing accuracy of comparison.
[5q f-48] The time to average displayed value at batch finish can be set. The
timing of batch finish delays for the time.
[Function] - [Function setting] - [Sequence] - [Timer] - [Average Eval time]
Changing the pulse width of batch finish output.
[5q f-43] If zero is set to this, the output remains until next start signal.
[Function] - [Function setting] - [Sequence] - [Timer] - [Batch finish output on]
Mixing at batch finish.
[5q f-14]
[Function] - [Function setting] - [Sequence] - [Control] - [Batch finish action]
Discharging at batch finish.
[5q f-15]
[Function] - [Function setting] - [Sequence] - [Control] - [Discharge finish
action]