Instruction manual

6-8
6-5 CALF-14=“3” Weighing Mode (with no Supplementary Flow)
(Normal batching in built-in automatic program mode)
Output signal Output condition
Zero band
Gross weight
Zero band
Full-flow Final -
Optional preliminary
Net weight
Medium-flow Final - Preliminary
Net weight
Dribble-flow Final - Free fall
Net weight
Over limit Final + Over limit < Net weight
Under limit Net weight < Final - Under limit
When an output condition is established, full flow, medium flow, and dribble flow outputs are turned off, but the other
outputs are turned on.
Once the full flow, medium flow, and dribble flow are turned off, they are not turned on until the next start of batching.
Over limit / Under limit is activated based on the net weight upon batch finish. (May be changed to customer
programmed control mode operation)
The zero band is a customer programmed control mode operation.
Weighing process
Sequence # Process
1
“Batch start” or “Discharge startsignal is ready to be input.
2
The “Batch start” signal is input.
The “Batch start wait timer” starts.
3
The “Batch start wait timer” completes the set time.
“Full-flow”, “Medium-flow” and “Dribble-flow” output signals are turned on.
The “Full-flow comparator inhibitor timer” and “Batch monitoring timer” start.
4
Net weight reaches the weight of “Final” –“Optional preliminary” or more.
The “Full-flow” output is turned off.
The “Medium-flow comparator inhibitor timer” start.
5
Net weight reaches the weight of “Final” –“Preliminary” or more.
The “Medium-flow” signal is turned off.
The “Dribble-flow comparator inhibitor timer” starts.
6
Net weight reaches the weight of “Final” –“Free fall” or more.
The “Dribble-flow” signal is turned off.
The “Judgment wait timer” starts.
7
The “Judgment wait timer” completes the set time.
Display becomes stable.
If automatic free fall compensation is being used, its calculation will be made.
The “Batch Finish” output signal is turned on
If there is excess or shortage, a judgment result output signal (over limit or under limit) will
be turned on. (“Within limit” is on in the chart on next page.)
The “Batch monitoring timer” is reset.
The net weight is accumulated automatically.
The data is output from the interface set for auto print.
8
The “Discharge start” signal is input.
The “Discharge start wait timer” starts.
9
The “Discharge start wait timer” completes the set time.
The “Discharge output“ signal is turned on.
The “Discharging time monitor timer” starts.
10
Gross weight reaches 0 or less.
The “Discharge valve close wait timer” starts.
The “Discharging time monitor timer” is reset.
11
The “Discharge valve close wait timer” completes the set time.
The “Discharge output “ signal is turned off.
12
The “Batch start” input signal for the next cycle is input.
The “Batch finish” output signal is turned off.
The judgment result output signal (Over limit or Under limit) is turned off.
* Now, the weighing sequence has cycled and restarts from sequence # 2 at this time.