Specifications
Altivar
®
31 Adjustable Speed AC Drives
Technical Specifications
© 2004–2005 Schneider Electric All Rights Reserved
8
4/2005
Internal supplies available
Short-circuit and overload protection:
One +10 V (-0 / +8%) supply for setpoint potentiometer (2.2 to 10 kΩ), maximum current 10 mA
One +24 V supply (minimum 19 V, maximum 30 V) for logic inputs, maximum current 100 mA
Configurable analog inputs
Three configurable analog inputs AI1, AI2, AI3.
AI1: Analog input 0 to +10 V (maximum safe voltage is 30 V)
• Impedance: 30 kΩ
• Resolution: 0.01 V, 10-bit converter
• Precision: ± 4.3% of maximum value
• Linearity: ± 0.2% of maximum value
• Sampling time: 8 ms
• Shielded cable length: 100 m (328 ft) maximum
AI2: Analog input 0 to +10 V (maximum safe voltage is 30 V)
Bipolar analog input 0 to ±10 V (maximum safe voltage is ±30 V)
The + or - polarity of the voltage on AI2 affects the direction of the setpoint and therefore the direction of rotation.
• Impedance: 30 k
Ω
• Resolution: 0.01 V, 10-bit + sign converter
• Precision: ± 4.3% of maximum value
• Linearity: ± 0.2% of maximum value
• Sampling time: 8 ms
• Shielded cable length: 100 m (328 ft) maximum
AI3: Analog input X–Y mA; X and Y programmable from 0–20 mA
• Impedance: 250
Ω
• Resolution: 0.02 mA, 10-bit converter
• Precision: ± 4.3% of maximum value
• Linearity: ± 0.2% of maximum value
• Sampling time: 8 ms
Analog output configurable for
voltage, current, or logic output
Analog output 0 to 10 V, minimum load impedance 470 Ω
or
Analog output X to Y mA; X and Y programmable from 0–20 mA, maximum load impedance 800
Ω:
• Resolution: 8 bits
• Precision: ± 1%
• Linearity: ± 0.2%
• Sampling time: 8 ms
or
AOC can be configured as a 24 V logic output with a minimum load impedance of 1.2 k
Ω.
Analog voltage output AOV
or
Analog current output AOC
or
Logic voltage output on AOC
Can assign either AOV or AOC, but not both.
Configurable relay outputs
R1A is a N.O. contact.
R1B is a N.C. contact.
R1C is the common.
R1 is programmable—factory set as a fault
relay (R1A is closed and R1B is open when the
controller is powered with no fault)
R2A, R2C
N.O. contact of programmable relay R2
• Minimum switching capacity: 10 mA for 5 Vdc
• Maximum switching capacity on a resistive load (power factor = 1 and L/R time constant = 0 ms):
5 A for 250 Vac and 30 Vdc
• Maximum switching capacity on an inductive load (power factor = 0.4 and L/R time constant = 7 ms):
1.5 A for 250 Vac and 30 Vdc
• Sampling time: 8 ms
• Service life: 100,000 operations at maximum switching power;
1,000,000 operations at minimum switching power
Logic inputs LI
Programmable logic inputs
• +24 V power supply (maximum 30 V)
• Impedance: 3.5 k
Ω
• State 0 if the difference between LIx and CLI is < 5 V, State 1 if the difference between LIx and CLI is > 11 V
• Sampling time: 4 ms
LI1, LI2, LI3, LI4, LI5, LI6
Maximum I/O connection capacity and
tightening torque
14 AWG (2.5 mm
2
)
0.6 N•m (5.31 lb-in)
Acceleration and deceleration ramps
Ramp profiles:
• linear, can be adjusted separately from 0.1 to 999.9 s
• S, U, or customized
Automatic adaptation of deceleration ramp time if braking capacities are exceeded,
possible inhibition of this adaptation (use of braking resistor).
DC injection braking
DC injection braking can be initiated:
• By a signal on a programmable logic input
• Automatically as soon as the estimated output frequency drops to < 0.5 Hz, period adjustable from 0 to 30 s or
continuous, current adjustable from 0 to 1.2 In
Signaling
on the drive local keypad display
• One red LED indicating the presence of drive voltage
• Four 7-segment displays
• Two CANopen status LEDs (RUN and ERR)
Scan time for reference change
5 ms
Electrical characteristics (continued)