Drive thermal protection
Thermal protection, by a PTC probe fitted on the heatsink or integrated into
the power module, ensures that the drive is protected in the event of poor
ventilation or excessive ambient temperatures.
The drive stops in the event of a fault.
R1/R2 relay configuration
The following states are signaled by powering up the relay:
drive faulted
drive running
frequency threshold reached
high speed reached
current threshold reached
frequency reference reached
motor thermal threshold reached
brake sequence activated (R2 only)
AOC/AOV analog output
The setting of this function modifies the characteristics of the current analog
output (AOC) or the voltage analog output (AOV).
AOC: adjustable as 0–20 mA or 4–20 mA
AOV: adjustable as 0–10 V
The same data is available on analog outputs AOC and AOV.
The following assignments are possible:
motor current
motor frequency
motor torque
power supplied by the drive
•drive fault
frequency threshold reached
high speed reached
current threshold reached
frequency reference reached
motor thermal threshold reached
brake sequence activated
Saving and retrieving the configuration
Saving a configuration to EEPROM allows you to keep a stored configuration
in addition to the current one.
Retrieving this configuration clears the current configuration.
5000
3000
1000
200
160
100
60
2
0
1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9
t
Motor current/Drive In
Trip time (s)
563532
Drive thermal protection
Configuring the AOC/AOV outputs in PowerSuite software