WIRING
Wiring diagram
Operation on an impedance grounded system
When using the ATV31 drive controller on a system with an isolated or impedance grounded neutral,
use a permanent insulation monitor compatible with non-linear loads.
ATV31••••M2 and N4 drives feature built-in RFI filters with grounded capacitors. When using the drive
on an impedance grounded system, we recommend isolating the RFI filters from ground to prevent
reduction of their operating life. For more information, refer to “Operation on an Impedance Grounded
System” in the Altivar
®
31 Installation Manual, bulletin number VVDED303041US.
U / T1
V / T2
W / T3
P0
PA / +
+10
AI1
COM
AI3
R / L1
S / L2
T / L3
R1A
R1C
R1B
LI1
CLI
R2A
R2C
LI2
LI3
LI4
LI5
LI6
24V
AI2
AOV
AOC
(2)
PB
PC / -
COM
A0C
(3)
U1
W1
V1
M
3 c
(5)
(1)
R / L1
S / L2
(4)
(1)
Reference
potentiometer
X–Y mA
ATV31••••M2
Single-phase supply
ATV31••••M3X/N4/S6X
Three-phase supply
Braking resistor,
if used
0 ± 10 V
Using the analog
output as
a logic output
24 V relay
or
24 V PLC input
or
LED
NOTE: The line supply terminals are shown at the top, and the motor
terminals are shown at the bottom. Use surge suppressors on all inductive
circuits located near the drive controller or coupled to the same circuit.
Refer to the Altivar
®
31 Installation Manual, VVDED303041US.
(1) Refer to the drive controller nameplate or to the fuse tables for recommended fuses.
Fast acting or time delay Class J fuses can be used.
(2) Fault relay contacts for remote indication of drive controller status.
(3) Internal +24 V. If an external source is used (30 V maximum), connect the 0 V terminal of
the source to the 0 V (COM) terminal, and do not use the +24 V terminal on the drive
controller for any purpose.
(4) Line reactor, if used. All 575 V installations must include a line reactor.
(5) Installation of a load filter is recommended for all 575 V applications.