Specifications

Altivar
®
31 Adjustable Speed AC Drives
Additional EMC Input Filters
17
4/2005 © 2004–2005 Schneider Electric All Rights Reserved
EMC filters
Drive
catalog
number
Maximum length of shielded cable
1
In
2
Il
3
Filter
catalog
number
Weight
EN 55011 Class A EN 55022 Class B
m (ft) m (ft) A mA kg (lb)
Single phase supply voltage: 200/240 V 50/60 Hz
ATV31H018M2
50 (164) 20 (66) 9 100 VW3A31401 0.600 (1.323)
ATV31H037M2
ATV31H055M2
ATV31H075M2
ATV31HU11M2
50 (164) 20 (66) 16 150 VW3A31403 0.775 (1.709)
ATV31HU15M2
ATV31HU22M2 50 (164) 20 (66) 22 80 VW3A31405 1.130 (2.491)
Three-phase supply voltage: 200/240 V 50/60 Hz
ATV31H018M3X
5 (16) 7 7 VW3A31402 0.650 (1.433)
ATV31H037M3X
ATV31H055M3X
ATV31H075M3X
ATV31HU11M3X
5 (16) 15 15 VW3A31404 1.000 (2.205)ATV31HU15M3X
ATV31HU22M3X
ATV31HU30M3X
5 (16) 25 35 VW3A31406 1.650 (3.638)
ATV31HU40M3X
ATV31HU55M3X
5 (16) 47 45 VW3A31407 3.150 (6.945)
ATV31HU75M3X
ATV31HD11M3X
5 (16) 83 15 VW3A31408 5.300 (11.684)
ATV31HD15M3X
Three-phase supply voltage: 380/500 V 50/60 Hz
ATV31H037N4
50 (164) 20 (66) 15 15 VW3A31404 1.000 (2.205)
ATV31H055N4
ATV31H075N4
ATV31HU11N4
ATV31HU15N4
ATV31HU22N4
50 (164) 20 (66) 25 35 VW3A31406 1.650 (3.638)ATV31HU30N4
ATV31HU40N4
ATV31HU55N4
50 (164) 20 (66) 47 45 VW3A31407 3.150 (6.945)
ATV31HU75N4
ATV31HD11N4
50 (164) 20 (66) 49 45 VW3A31409 4.750 (10.472)
ATV31HD15N4
1)
For a switching frequency of 2 to 16 kHz. These limits are given as examples only, as they vary depending on the interference
capacity of the motors and the cables used. If motors are connected in parallel, it is the total length that should be considered.
2)
In: Nominal filter current.
3)
Maximum earth leakage current at 50 Hz.
VW3A31403 16A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com