Specifications

Altivar
®
31 Adjustable Speed AC Drives
Additional EMC Input Filters
© 2004–2005 Schneider Electric All Rights Reserved
16
4/2005
The kits in the following table use the thermal protection of a GV2 manual starter and have a Type 1
rating per UL 50. The insulation system is suitable for use in a Pollution Degree 3 environment (refer to
NEMA ICS-1 Annex A). The package is UL/CSA marked.
ADDITIONAL EMC INPUT FILTERS
Function
The ATV31 drive has built-in radio frequency interference (RFI) input filters to meet EMC “product”
standards for adjustable speed drives, IEC/EN 61800-3, and to comply with the European EMC
(electromagnetic compatibility) directive.
The additional filters enable the drives to meet more stringent requirements: they are designed to
reduce conducted emissions on the line supply below the limits of standards EN 55011 class A (1) or
EN 55022 class B. These filters mount beneath ATV31H drives via tapped holes, acting as supports for
the drives.
Considerations for isolated or impedance grounded neutral systems
The standard IEC 61800-3, annex D2.1, indicates that on isolated or impedance grounded neutral
systems, the filters can affect the operation of insulation monitors.
The efficiency of additional filters on this type of system also depends on the nature of the impedance
between neutral and earth and is therefore unpredictable.
If installing a machine on an isolated or impedance grounded neutral system, one solution is to insert an
isolation transformer and connect locally to the machine on a neutral connection or neutral-to-earth system.
Dynamic braking resistor kits technical specifications
Drive controller
catalog number
Ohmic Value
(Rdb)
Ω
Continuous Current
Rating of Assembly (Ir)
A
Average
Power
W
Kit catalog
number
ATV31H018M2–037M2
ATV31H018M3X–037M3X
ATV31H037N4–U40N4
120 1.00 120 VW3A66711
ATV31H055M2–U22M2
ATV31H055M3X–U22M3X
ATV31HU55N4–U75N4
56 1.45 118 VW3A66712
ATV31HU30M3X–U40M3X
ATV31HD11N4–D15N4
28 2.70 204 VW3A66713
ATV31HU55M3X–U75M3X 14 3.80 202 VW3A66714
ATV31HD11M3X–D15M3X 10 10.00 1000 VW3A66715
Characteristics
Conformity to standards
EN 133200
Degree of protection
IP 21 and IP 41 on upper part
Maximum relative humidity
93% without condensation or dripping water conforming to IEC 68-2-3
Ambient air temperature
around the device
Operation -10 to +60 °C (14 to +140 °F)
Storage -25 to +70 °C (-13 to +158 °F)
Maximum operating altitude
Without derating 1000 m (3281 ft). At higher elevations, derate the current by 1% per additional 100 m (328 ft).
Vibration resistance
Conforming to IEC 60068-2-6
1.5 mm peak to peak from 3 to 13 Hz
1 gn peak from 13 to 150 Hz
Shock resistance
Conforming to IEC 60068-2-27 15 gn for 11 ms
Maximum nominal voltage
50/60 Hz single phase 240 V +10%
50/60 Hz three-phase
240 V +10%
500 V +10%
600 V +10%
VW3A31402 7A