Specifications
Altivar
®
31 Adjustable Speed AC Drives
Selection
11
4/2005 © 2004–2005 Schneider Electric All Rights Reserved
1)
A 3% line reactor is required for all 575 V drive controller installations.
2)
For a drive equipped with a control potentiometer and with run and stop buttons, add an “A” at the end of the catalog number (for
example, ATV31HO37N4A). This option is not available for 575 V controllers.
3)
These power ratings and currents are for a maximum ambient temperature of 50 °C (122 °F) and a switching frequency of 4 kHz
in continuous operation. The switching frequency is adjustable from 2 to 16 kHz. Above 4 kHz, the drive controller reduces the
switching frequency in the event of excessive temperature rise. The temperature rise is controlled by a PTC probe in the power
module. Derate the nominal current if continuous operation above 4 kHz is required. Derating curves are shown on page 30 as a
function of switching frequency, ambient temperature, and mounting conditions.
4)
Current on a line supply with the indicated short-circuit current rating.
5)
Peak current on power-up, for the maximum voltage (460 Vac/575 Vac +15%).
6)
For 60 seconds.
7
Refer to “Recommended fuses or Powerpact
®
circuit breakers” on page 26.
400 V -15% / 460 V +15% at 50/60 Hz, three-phase input, three-phase output
ATV31 drive Motor Line supply (input) Drive controller (output)
Catalog
number
2
Power
indicated on
nameplate
3
Max. line
current
4
Short-
circuit
current
rating
7
Max.
inrush
current
5
Nominal
rated output
current In
3
Max.
transient
current
3,6
Total
dissipated
power at
rated load
at
400 V
at
460 V
kWhpAAkA A A A W
ATV31H037N4 0.37 0.5 2.2 1.7 5 10 1.5 2.3 32
ATV31H055N4 0.55 0.75 2.8 2.2 5 10 1.9 2.9 37
ATV31H075N4 0.75 1 3.6 2.7 5 10 2.3 3.5 41
ATV31HU11N4 1.1 1.5 4.9 3.7 5 10 3.0 4.5 48
ATV31HU15N4 1.5 2 6.4 4.8 5 10 4.1 6.2 61
ATV31HU22N4 2.2 3 8.9 6.7 5 10 5.5 8.3 79
ATV31HU30N4 3 3 10.9 8.3 5 10 7.1 10.7 125
ATV31HU40N4 4 5 13.9 10.6 5 10 9.5 14.3 150
ATV31HU55N4 5.5 7.5 21.9 16.5 22 30 14.3 21.5 232
ATV31HU75N4 7.5 10 27.7 21.0 22 30 17.0 25.5 269
ATV31HD11N4 11 15 37.2 28.4 22 97 27.7 41.6 397
ATV31HD15N4 15 20 48.2 36.8 22 97 33.0 49.5 492
525 V -15% / 575 V +15% at 50/60 Hz, three-phase input, three-phase output
1
ATV31 drive Motor Line supply (input) Drive controller (output)
Catalog
number
2
Power
indicated on
nameplate
3
Max. line
current
4
Short-
circuit
current
rating
7
Max.
inrush
current
5
Nominal
rated output
current In
3,6
Max.
transient
current
3,6
Total
dissipated
power at
rated load
at
525 V
at
600 V
kWhpAAkA A A A W
ATV31H075S6X 0.75 1 2.8 2.4 5 12 1.7 2.6 36
ATV31HU15S6X 1.5 2 4.8 4.2 5 12 2.7 4.1 48
ATV31HU22S6X 2.2 3 6.4 5.6 5 12 3.9 5.9 62
ATV31HU40S6X 4 5 10.7 9.3 5 12 6.1 9.2 94
ATV31HU55S6X 5.5 7.5 16.2 14.1 22 36 9.0 13.5 133
ATV31HU75S6X 7.5 10 21.3 18.5 22 36 11.0 16.5 165
ATV31HD11S6X 11 15 27.8 24.4 22 117 17.0 25.5 257
ATV31HD15S6X 15 20 36.4 31.8 22 117 22.0 33.0 335
ATV31HU75N4
531250-20-M.tif
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com