Specifications
3 V-Server
3-3
3
Q3 The monitored device comes to a STOP state on V-Server.
A3 Check the following:
• If the monitored device (V series /HMI-mode TELLUS) is in a STOP state (on the [Main Menu] (local
main) screen), V-Server will also be brought to a STOP state. Change the state of the monitored device
to RUN.
• Is the IP address of the monitored device correct?
In the [Property] dialog box for the monitored device, set the IP address of the V series (HMI-mode
TELLUS). Be sure to set the IP address correctly in the dialog box.
To see the V-series IP address, go to the [Main Menu] (local main) screen.
To see the HMI-mode TELLUS IP address, go to [Tellus Version Information] using the [Help] icon.
• Is the port number of the monitored device correct?
In the [Property] dialog box for the monitored device, set the port number of the V series (HMI-mode
TELLUS).
Be sure to set the port number correctly in the dialog box.
To see the V-series port number, go to the [Main Menu] (local main) screen. (See the above figure.)
To see the HMI-mode TELLUS port number, go to [Tellus Version Information] using the [Help] icon.
(See the figure below.)
POWER
F1
F2
F3
F4
F5
F6
F7
SYSTEM
: 100BASE-T
: 192.168.1.68
2005-9 -5 09:23:30
SYSTEM PROG. VER. 1.519
FONT
VER.1.330/1.100/1.000
JAPANESE 32
I/F DRV VER.1.310
MELSEC AnA/N/U
Editor:MJ1
Main Menu
V710iT
System Information
PLC Type : MITSUBISHI A Series link
Comment :
Screen Data
Information
Size: 5832704
SRAM/Clock
Ethernet
Card
Menu
I/O Test
Ethernet Information
Trans.Speed
Stat. No.
PORT : 10000
MAC : 0050FF000035
1:1
RS232C
0
Baud Rate :
Data Lebgth :
Stop Bit :
Parity :
Send Delay :
19200
7
1
Even
0 msec
Connection :
Signal Level :
PLC Stat.No. :
Stop
0.50 sec
3
Error :
Time-Out :
Retry :
RGB
Adjustment
Extension
Program Info.
V series
V-Server [Property] dialog box
for monitored device
Set the same
number.